SIEP C730600 0DB EtherNet/IP Technical Manual
Status
Fault Declared
Status
Value (U6-
98/U6-99)
Description
Communications time-out (non-
fatal)
bUS
1101
The node timer (Requested Packet Interval) timed out.
Duplicate IP Address
bUS
1102
This node and at least one other node have the same IP Address.
Default MAC Address
-
1103
Factory default MAC Address programmed into the option.
Note:
Return the option to Yaskawa or your nearest sales representative and request the setting
change.
Two drive monitor parameters,
U6-98 [First Fault]
and
U6-99 [Current Fault]
assist the user in network
troubleshooting.
•
U6-98
displays the first declared fault since the last power cycle.
U6-98
is only cleared upon drive power-up.
•
U6-99
displays the present option status.
U6-99
is cleared upon a network-issued fault reset and upon power-up.
If another fault occurs while the original fault is still active, parameter
U6-98
retains the original fault value and
U6-99
stores the new fault status value.
◆
Option Compatibility
You can connect a maximum of 3 options at the same time depending on the type of option.
Note:
•
You can only connect one option to the GA500 and HV600 drives. Connect the option to the CN5 connector.
•
You can connect two options to an FP605 drive. Connect the communication option to the CN5-A connector.
•
Compatible communication options are different for different models. Refer to the drive manuals for more information.
Table 16.3 Option Compatibility
Option
Connector
Number of Options Possible
PG-B3
, PG-X3
CN5-B, C
2
PG-RT3
, PG-F3
CN5-C
1
DO-A3
, AO-A3
CN5-A, B, and C
1
SI-C3, SI-N3, SI-P3, SI-S3, SI-T3, SI-ET3,
SI-ES3, SI-B3, SI-M3,
SI-W3
, SI-EM3
, SI-EM3D
, SI-EN3D
, SI-
EP3, JOHB-SMP3,
, DI-A3
CN5-A
1
*1
Not available for GA500, HV600, or FP605 drives.
*2
To connect two PG options, use the CN5-C and CN5-B connectors. To connect only one PG option, use the CN5-C connector.
*3
If you use the motor switching function, you cannot use this option.
*4
Not available for 1000-Series drive models with capacities between 450 and 630 kW (650 to 1000 HP).
*5
Not available for GA500 or HV600 drives.
*6
To use AI-A3 and DI-A3 input statuses as monitors, connect the options to CN5-A, CN5-B, or CN5-C.
17
Option Installation
Verify the following installation conditions to make sure that other devices and machinery used with this option
and drive also comply with EMC guidelines:
1.
Use dedicated shield cable for the option and external device (encoder, I/O device, master), or run the
wiring through a metal conduit.