bUS Fault Tolerance
■
bUS Fault Auto-Restart
Parameter
F6-14 [bUS Fault Auto Reset Select]
will appear when the option is installed.
Setting
F6-14 = 0 [Disabled]
or
F6-01 = 3 or greater (Alarm only)
will not affect standard default drive behavior.
Setting
F6-14 = 1 [Enabled]
AND
F6-01 ≠ 3 [Fault]
will cause the following operation:
1. The bUS fault occurs after the
F7-16 [Timeout Value]
delay and the Run command is removed from the drive.
2. Then the option throws a
bUS
fault to the drive.
3. When the condition is removed, the option commands a fault reset and returns control of the drive to the
EtherNet/IP network.
Note:
The option will only read parameter
F6-01
and
F6-14
from the drive during power-up.
■
bUS Fault Delay
Parameter
F7-16 [Timeout Value]
will appear when the option is installed. The setting value of
F7-16
is the length
of time that the option will delay sending the
bUS
fault to the drive. The status LEDs on the option are not
affected by the delay time set in
F7-16
; the LEDs will indicate the
bUS
condition immediately.
Note:
The option will only read parameter
F7-16
from the drive during power-up.
◆
Explicit Message Communications Errors
When there is a problem with a request message sent from the master in explicit communications, the drive will
return one of the error codes shown in
.
Table 16.1 Communications Errors and Solutions
Error Code
(Hex.)
Description
Cause
Possible Solutions
08
Service not supported
The service code is incorrect.
Correct the service code.
09
Invalid attribute value
The attribute is incorrect.
Correct the attribute.
0C
Object state conflict
Attempted to change a drive parameter that cannot be
changed while the drive is running.
Stop the drive.
0E
Attribute not settable
Attempted to change a read-only attribute.
Correct the service code or attribute setting.
13
Not enough data
The data size is incorrect.
Correct the data size.
14
Attribute not supported
Attempted to execute a service not defined for the attribute. Correct the service code or attribute setting.
15
Too much data
The data size is incorrect.
Correct the data size.
16
Object does not exist
An unsupported object was specified.
Correct the class or instance setting.
1F
Vendor-specific error
•
Attempted to change a drive parameter that cannot be
changed while the drive is running.
•
Attempted to change a drive parameter to a value
outside the setting range.
•
Stop the drive.
•
Specify a value within the setting range.
20
Invalid parameter
Attempted to change to a data value outside the setting
range.
Specify a data value within the setting range.
◆
Option Error Codes
■
Option Fault Monitors
U6-98
and
U6-99
The option can declare error/warning conditions via drive monitor parameters on the drive keypad as shown in
Table 16.2 Option Fault Monitor Descriptions
Status
Fault Declared
Status
Value (U6-
98/U6-99)
Description
No faults
-
0
No faults
Fatal error occurred
EF0
3
Network sent a message to force this node to the fault state.
Network Link Down
bUS
1100
No network link to option.