5 Installation Procedure
YASKAWA ELECTRIC
TOBP C730600 60A V1000 Option EtherNet/IP Installation Manual
EN 19
Figure 5
Figure 5 Remove the Bottom Cover on an IP20/Open-Chassis Drive
(Models CIMR-V
BA0001B to BA0003B and 2A0001B to 2A0006B)
Figure 6
Figure 6 Remove the Terminal Cover and Bottom Cover on
an IP20/Open-Chassis Drive (Models CIMR-V
BA0006B to
BA0018B; 2A0008B to 2A0069B; 4A0001B to 4A0038B)
4.
On IP20/Open-Chassis models, connect the drive side of the ground wire to the
drive ground terminal.
Note:
The four different ground wires packaged with the option connect the option to different drive
models. Select the proper ground wire depending on drive size. Refer to
Table 7
for ground wire
selection by drive model.
Figure 7
Figure 7 Connect the Ground Wire on an IP20/Open-Chassis Drive
V1000
Bottom Cover
Terminal Cover
V1000
Ground terminal
Ground wire
Ground wire
Drive-side
connector
Screw size:
M3.5 to M6
Option unit
connector
Screw size: M3
V1000