TOEP C730600 91B Modbus TCP/IP Installation Manual
67
Option
Connector
Number of Options
Possible
DO-A3
, AO-A3
CN5-A, B, and C
1
SI-C3, SI-N3, SI-P3, SI-S3, SI-T3, SI-ET3,
SI-ES3, SI-B3, SI-M3,
SI-W3
, SI-EM3
, SI-
EN3
, SI-EN3D
, SI-EP3, JOHB-
SMP3,
AI-A3
, DI-A3
CN5-A
1
*1
Not available for GA500, HV600, or FP605 drives.
*2
To connect two PG options, use the CN5-C and CN5-B connectors. To connect only one PG option, use the
CN5-C connector.
*3
If you use the motor switching function, you cannot use this option.
*4
Not available for 1000-Series drive models with capacities between 450 and 630 kW (650 to 1000 HP).
*5
Not available for GA500 or HV600 drives.
*6
To use AI-A3 and DI-A3 input statuses as monitors, connect the options to CN5-A, CN5-B, or CN5-C.
10
Option Installation
Verify the following installation conditions to make sure that other devices and machinery
used with this option and drive also comply with EMC guidelines:
1.
Use dedicated shield cable for the option and external device (encoder, I/O
device, master), or run the wiring through a metal conduit.