Sigma II User’s Manual
Chapter 9: Inspection, Maintenance, and Troubleshooting
9 - 8
A.10
A.10: Overcurrent or Heat Sink Overheated
Display and Outputs
Note:
OFF:
Output transistor is OFF (alarm state).
ON:
Output transistor is ON.
Status and Remedy for Alarm
Note:
Problems E to H can occur in a servo amplifier with a capacity of
1.5 to 5kW, and all 400V models.
Alarm Outputs
Alarm Code Output
ALM Output
ALO1
ALO2
ALO3
ON
OFF
OFF
OFF
Cause of the Problem
Solution
A
Shorted wiring between servo
amplifier and servomotor.
Check and correct wiring.
B
Shorted servomotor U, V, or W
phase.
Replace servomotor.
C
• Defective circuit board (1PWB)
.
• Defective power transistor.
Replace servo amplifier.
D
Defective current feedback circuit,
power transistor, DB circuit, or cir-
cuit board.
Replace servo amplifier.
E
Ambient temperature of the servo
amplifier greater than 55°C.
Alter conditions so that the ambi-
ent temperature is below 55°C.
F
Inadequate air flow around the
heat sink.
Providing sufficient space as
specified.
G
Fan stopped.
Replace servo amplifier.
H
Servo amplifier is operating under
an overload.
Reduce load.
When Servo ON (S-ON)
At power ON.
During servomotor
operation.
ssignal is turned ON.
A, B, D,
C
C, D
E, F, G
Summary of Contents for SGMAH
Page 1: ...Sigma II Series Servo System User s Manual...
Page 2: ......
Page 4: ...ii This page intentionally left blank...
Page 6: ...iv This page intentionally left blank...
Page 10: ...Sigma II User s Manual Table of Contents Preface viii Notes...
Page 17: ...Sigma II User s Manual Table of Contents Preface xv C 6 Torque Control Mode C 9...
Page 18: ...Sigma II User s Manual Table of Contents Preface xvi...
Page 38: ...Sigma II User s Manual Chapter 2 Installation 2 10 NOTES...
Page 472: ...Sigma II User s Manual Appendix C Examples of Standard Connections C 10 Notes...
Page 487: ......