7 Set-up Procedure for Fully-closed Loop Control
7.2.2 Sigma-5 SERVOPACK Set-up for Fully-Closed Loop Control
7-8
7.2.2
Sigma-5 SERVOPACK Set-up for Fully-Closed Loop Control
According to applications, these parameters should be set for the correct operation of Sigma-5 with the option
modules. The detailed usage for each parameter is shown in section 7.2.2 Sigma-5 SERVOPACK Set-up for
Fully-Closed Loop Control 7-8.
*1 these settings are dependent on the applications
Parameter
Function
Default
Value
Required
value
Cat.
When enabled
No.
Dig.
Pn000
Basic Function Select Switch 0
-
-
-
-
0
Direction Selection
0
*1
O
After restart
0
Forward command for forward direction
1
Forward command for reverse direction
Pn002
Application Function Select Switch 2
-
-
-
-
2
Absolute Encoder Usage
0
*1
O
After restart
0
Uses absolute encoder as an absolute
encoder
1
Uses absolute encoder as an incremental
encoder
3
External Encoder Usage
0
1 or 3
M
After restart
0
Do not use external encoder
1
Uses external encoder in forward rotation/
movement direction
2
Reserved (Do not change.)
3
Uses external encoder in reversed rotation/
movement direction
4
Reserved (Do not change.)
Pn00B
Application Function Select Switch B
-
-
-
-
3
Feedback Option Module Usage
0
0
M
After restart
0
Uses for external encoder feedback
1
Uses for motor encoder feedback
Pn081
Application Function Select Switch 81
-
-
-
-
1
Encoder Pulse Output Usage
0
*1
O
After restart
0
Enables the pulse output function (Pn281)
1
Disables the pulse output function
Pn20A
Number of External Encoder Period
32768
*1
M
After restart
Pn281
Encoder Output pulses [Pulse edge/Period]
20
*1
O
After restart