STEP 5: DynaPower DC/DC Converter Conductor Termination
The Re-Combiner is supplied with 20-foot pigtail conductors for the wiring to the
Dynapower DC/DC Converter. These conductors are pre-terminated inside the Re-
Combiner; the pigtail conductors are provided looped and secured temporarily outside
of the unit. The user is responsible to route, secure and properly terminate these
conductors to the Dynapower DC/DC Converter.
Conductors
Factory Pre-Wired DynaPower DC/DC Converter Terminations inside the Re-Combiner
Max Output
Current
DPS-500: 500 A
DPS-375/250: 312.5A
DC Re-
Combiner No.
of Terminals
2 per pole (2 pos, 2 neg)
Supplied
Conductors
350kcmil, 90C rated
2 per Pole (as in Fig. 5.5)
+
_
See the DynaPower DC/DC Converter Installation User Manual for making
connections to that unit. No field-wiring inside the Re-Combiner is required
for the Dynapower DC/DC Converter.