2.8 General data
Conformity and approval
Conformity
CE
2014/35/EU
Low-voltage directive
2014/30/EU
EMC directive
Approval
UL
-
Refer to Technical data
others
RoHS
2011/65/EU
Restriction of the use of certain hazardous substances in
electrical and electronic equipment
Protection of persons and device protection
Type of protection
-
IP20
Electrical isolation
Safe insulation
-
between primary and secondary side
Insulation voltage to reference earth
Inputs / outputs
-
Protective measures
-
against short circuit
Environmental conditions to EN 61131-2
Climatic
Storage / transport
EN 60068-2-14
-40…+80°C
Operation
Horizontal installation hanging
EN 61131-2
0…+60°C
Vertical installation
EN 61131-2
0…+50°C
Air humidity
EN 60068-2-30
RH1 (without condensation, rel. humidity 5…95%)
Pollution
EN 61131-2
Degree of pollution 2
Installation altitude max.
-
2000m
Mechanical
Oscillation
EN 60068-2-6
1g, 9Hz ... 150Hz
Shock
EN 60068-2-27
15g, 11ms
Mounting conditions
Mounting place
-
In the control cabinet
Mounting position
-
Horizontal and vertical
VIPA System MICRO
Basics and mounting
General data
HB400 | PS | M07-2BA00 | en | 20-02
21