8
YASKAWA ELECTRIC
TOBP C730600 55A 1000-Series Option PS-A10 Installation Manual
2 Product Overview
2
Product Overview
◆
About this Product
The 24 V Power Supply option maintains drive control circuit power in the event of a main
power outage. As long as the control circuit has power, network communications and I/O
data remain operational. The option provides external power to the control circuit only, and
does not provide power to the main circuit of the drive.
It is possible to read fault and parameter data in the drive via the operator or network
communications when the drive switches to the option as a back-up power supply.
Note: 1.
Parameter settings cannot be changed without drive main circuit power regardless of whether the
control circuit has enough power to operate.
2.
When connecting the 24 V Power Supply Unit, set the drive Undervoltage Detection Level (Uv) to its
default value.
◆
Applicable Models
The 24 V Power Supply Option can be used with the drive models in
.
Table 1 Applicable Models
Drive Series
Drive Voltage Class
Option Model
A1000
200 V Class
PS-A10LB
400 V Class
PS-A10HB
600 V Class
L1000A
200 V Class
PS-A10LB
400 V Class
PS-A10HB
T1000A
200 V Class
PS-A10LB
400 V Class
PS-A10HB
Z1000
200 V Class
PS-A10LB
400 V Class
PS-A10HB