Drive Model
Terminal
Recomm. Gauge
AWG, kcmil
Wire Range
AWG, kcmil
Screw
Size
Tightening Torque
N·m (lb.in.)
4A0930
R/L1, S/L2, T/L3, R1/L11, S1/L21,
T1/L31
4/0 × 4P×2
3/0 to 300
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3
4/0 × 4P×2
3/0 to 300
⊖
,
⊕
1
–
4/0 to 300
⊕
3
–
4/0 to 300
3/0
3/0 to 250
4A1200
R/L1, S/L2, T/L3, R1/L11, S1/L21,
T1/L31
300 × 4P×2
4/0 to 300
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3
300 × 4P×2
4/0 to 300
⊖
,
⊕
1
–
250 to 300
⊕
3
–
4/0 to 300
4/0
4/0 to 250
<1> Install a GFCI when using this wire gauge in accordance with IEC/EN 61800-5-1.
<2> Install a GFCI or use 10 mm
(AWG 8) copper wire when using this wire gauge in accordance with IEC/EN 61800-5-1.
Note:
When connecting peripheral devices or options to terminals
⊖
,
⊕
1,
⊕
3, B1, and B2, refer to the instruction manual for each device. For
more information, contact Yaskawa or your nearest sales representative.
n
Three-Phase 600 V Class
Table 3.5 Wire Gauge and Torque Specifications (Three-Phase 600 V Class)
Drive Model
Terminal
Recomm. Gauge
mm
2
(AWG, kcmil)
Wire Range
mm
2
(AWG, kcmil)
Screw
Size
Tightening Torque
N·m (lb.in.)
5A0003
5A0004
5A0006
R/L1, S/L2, T/L3
2.5
(14)
2.5 to 6.0
(14 to 10)
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/T3
2.5
(14)
2.5 to 6.0
(14 to 10)
⊖
,
⊕
1,
⊕
2
–
2.5 to 6.0
(14 to 10)
B1, B2
–
2.5 to 6.0
(14 to 10)
6.0
(10)
2.5 to 6.0
(14 to 10)
5A0009
R/L1, S/L2, T/L3
2.5
(14)
2.5 to 6.0
(14 to 10)
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/T3
2.5
(14)
2.5 to 6.0
(14 to 10)
⊖
,
⊕
1,
⊕
2
–
2.5 to 6.0
(14 to 10)
B1, B2
–
2.5 to 6.0
(14 to 10)
6.0
(10)
4.0 to 6.0
(12 to 10)
5A0011
R/L1, S/L2, T/L3
6.0
(10)
2.5 to 16
(14 to 6)
M4
2.1 to 2.3
(18.6 to 20.4)
U/T1, V/T2, W/T3
2.5
(14)
2.5 to 16
(14 to 6)
⊖
,
⊕
1,
⊕
2
–
2.5 to 16
(14 to 6)
B1, B2
–
2.5 to 6.0
(14 to 10)
10
(8)
4.0 to 6.0
(12 to 8)
M5
2.0 to 2.5
(17.7 to 22.1)
3.8 Main Circuit Wiring
90