A.2 Parameter Table
YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
349
Para
me
te
r Lis
t
A
L6-08
Mechanical
Weakening (OL5)
Detection Operation
This function can detect an over/undertorque in
a certain speed range as a result of machine
fatigue. It is triggered by a certain operation
time and uses the OL1 detection settings (L6-01
to L6-03)
0: Mechanical Weakening Detection disabled.
1: Continue running if the speed (signed) is
greater than L6-09 (alarm only).
2: Continue running if the speed (not signed) is
greater than L6-09 (alarm only).
3: Interrupt drive output when the motor speed
(signed) is greater than L6-09 (protection
operation).
4: Interrupt drive output when the motor speed
(not signed) is greater than L6-09 (protection
operation).
5: Continue running if the speed (signed) is less
than L6-09 (alarm only).
6: Continue running if the speed (not signed) is
less than L6-09 (alarm only).
7: Interrupt drive output when the motor speed
(signed) is less than L6-09 (protection
operation).
8: Interrupt drive output when the motor speed
(not signed) is less than L6-09 (protection
operation).
0 to 8
0
A A A
468
L6-09
Mechanical
Weakening Detection
Speed Level
Sets the speed that triggers mechanical
weakening detection.
When L6-08 is set for an unsigned value, the
absolute value is used even if the setting is
negative.
-110.0 to
+110.0%
110% A A A
469
L6-10
Mechanical
Weakening Detection
Time
Sets the time a mechanical weakening has to be
detected before an Alarm/Fault is triggered.
0.0 to
10.0 s
0.1 s A A A
46A
L6-11
Mechanical
Weakening Detection
Start Time
Sets the operation time (U1-04) that has to be
passed before Mechanical weakening detection
is active.
0 to
65535
0
A A A
46B
No.
Name
Description
Range Def.
Control
Mode
Addr.
Hex
Pg.
V/f
O
LV
P
M