A.2 Parameter Table
YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
303
Para
me
te
r Lis
t
A
b5-05
Derivative Time (D)
Sets D control derivative time. A setting of 0.00
s disables derivative control.
0.00 to
10.00
0.00
s
A A A
1A9
b5-06
PID Output Limit
Sets the maximum output possible from the
entire PID controller.
0.0 to
100.0
100.0
%
A A A 1AA
b5-07
PID Offset
Adjustment
Applies an offset to the PID controller output.
-100.0 to
+100.0
0.0% A A A 1AB
b5-08
PID Primary Delay
Time Constant
Sets the amount of time for the filter on the
output of the PID controller.
0.00 to
10.00
0.00
s
A A A 1AC
b5-09
PID Output Level
Selection
Sets the PID controller output direction.
0: Normal Output (direct acting)
1: Reverse Output (reverse acting)
0,1
0
A A A 1AD
b5-10
PID Output Gain
Setting
Sets the gain applied to the PID output.
0.00 to
25.00
1.00 A A A 1AE
b5-11
PID Output Reverse
Selection
Sets the drive operation with negative PID
output.
0: Drive stops with negative PID output
1: Rotation direction reverses with negative
PID output.
When using setting 1 make sure, reverse
operation is permitted by parameter b1-04.
0,1
0
A A A 1AF
b5-12
PID Feedback
Reference Missing
Detection Selection
Configures the PID feedback loss
detection.With all setting a digital output
programmed for H2-01/02/03 = 3E/3F (PID
feedback low/PID feedback high) is operated
when the detection condition becomes true.
0: Digital output only.
1: Feedback loss detected when PID enabled.
Alarm output, operation is continued without
triggering a fault contact.
2: Feedback loss detected when PID enabled.
Fault output, operation is stopped and a fault
contact is triggered.
3: Feedback loss detection even when PID is
disabled by digital input. No alarm/fault output.
4: PID Feedback error detection even when PID
is disabled by digital input. An alarm is
triggered and the drive continues to run.
5: PID Feedback error detection even when PID
is disabled by digital input. Fault is triggered
and output is shut off.
0 to 5
0
A A A
1B0
b5-13
PID Feedback Loss
Detection Level
Sets the PID feedback loss detection level.
0 to 100 0% A A A
1B1
No.
Name
Description
Range Def.
Control
Mode
Addr.
Hex
Pg.
V/f
O
LV
P
M
Summary of Contents for OYMC V1000
Page 2: ...2 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual...
Page 8: ...8 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual INDEX 393...
Page 407: ...YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual 407...