A.2 Parameter Table
300
YASKAWA ELECTRIC
SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
b1-14
Phase Order Selection
Sets the phase order for drive output terminals
U/T1, V/T2 and W/T3.
0: Standard
1: Switch phase order
0,1
0
A A A
1C3
b1-15
Frequency
Reference 2
Selects the frequency reference input source.
0: Operator - Digital preset speed d1-01 to d1-
17.
1: Terminals - Analog input terminal A1 or A2
2: Memobus communications
3: Option PCB
4: Pulse Input (Terminal RP)
0 to 4
0
A A A
1C4
b1-16
Run Command Source
2
Selects the run command input source.
0: Operator - RUN and STOP keys on the
digital operator.
1: Digital input terminals
2: Memobus communications
3: Option PCB
0 to 3
0
A A A
1C5
b1-17
Run Command at
Power Up
Determines the operation when a Run
command is active at power up of the drive.
0: Run command not issued, needs to be cycled
1: Run command issued, motor operation start
0,1
0
A A A
1C6
b2: DC Injection Braking
Use b2 parameters to configure DC Injection Braking operation
b2-01
DC Injection Braking
Start Frequency
Sets the frequency at which DC Injection
Braking starts when Ramp to Stop (b1-03 = 0)
is selected. If b2-01< E1-09, DC Injection
Braking starts at E1-09.
0.0 to
10.0
0.5
Hz
A A A
189
b2-02
DC Injection Braking
Current
Sets the DC Injection Braking current as a
percentage of the drive rated current.
0 to 75 50% A A
−
18A
b2-03
DC Injection Braking
Time/DC Excitation
Time at Start
Sets DC Injection Braking time at start.
Disabled when set to 0.00 seconds.
0.00 to
10.00
0.00
s
A A
−
18B
b2-04
DC Injection Braking
Time at Stop
Sets DC Injection Braking time at stop.
When b1-03 = 2, actual DC Injection time is
calculated as follows:
(b2-04) x 10 x (Output Freq) / (E1-04).
When b1-03 = 0, this parameter sets the amount
of DC Injection time applied to the motor at the
end of the decel ramp or High Slip Braking.
Disabled when set to 0.00.
0.00 to
10.00
0.50
s
A A
−
18C
No.
Name
Description
Range Def.
Control
Mode
Addr.
Hex
Pg.