1.8 L: Protection Functions
204
YASKAWA ELECTRIC
SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
Setting 0: Disabled
The level set in L3-06 is used throughout the entire speed range.
Setting 1: Enabled
The Stall Prevention level during run is reduced in the constant power range. The lower limit
will be 40% of L3-06.
■
Overvoltage Suppression Function
This function suppresses overvoltage faults by slightly increasing the output frequency when
the DC bus voltage rises. It can be used to drive loads with cyclic regenerative operation,
such as punch presses or other applications that involve repetitive crank movements.
The output frequency is adjusted during OV suppression so that the DC bus voltage does not
exceed the level set in parameter L3-17. Besides the parameters explained below, OV
suppression uses the following settings for frequency adjustment:
• DC bus voltage gain L3-20
• Deceleration rate calculations gain L3-21
• Inertia calculations for motor acceleration time L3-24
• Load inertia ratio L3-25
Note:
1.
The motor speed will exceed the frequency reference when overvoltage suppression is triggered.
Consequently, overvoltage suppression is not appropriate in applications that require a perfect match
between the frequency reference and the actual motor speed.
2.
Disable overvoltage suppression when using a braking resistor.
3.
Overvoltage may still occur if there is a sudden increase to a regenerative load.
4.
This function is enabled only when operating just below the maximum frequency. Overvoltage
suppression does not increase the output frequency beyond the maximum frequency. If this is required
by the application increase the maximum frequency and change the base frequency setting.
■
L3-11: Overvoltage Suppression Function Selection
Enables or disables the overvoltage suppression function.
Setting 0: Disabled
The output frequency is not adjusted. A regenerative load may trip the drive with an
overvoltage fault. Use this setting if braking options are installed.
Setting 1: Enabled
When the DC bus voltage rises due to regenerative load, an overvoltage fault is prevented by
increasing the output frequency.
■
L3-17: Desired DC Bus Voltage for Overvoltage Suppression and Stall
No.
Name
Setting Range
Default
L3-11
OV Suppression Function Selection
0 or 1
0