8 Troubleshooting
YASKAWA ELECTRIC
TOBP C720600 01E YASKAWA AC Drive Option CDBR-
D, LKEB-
Installation Manual
61
The CDBR braking unit is not
operating.
• A master unit is incorrectly set to
be a slave device and there is no
master unit.
• Incorrect braking activation switch
position.
• Properly set the CDBR braking unit
Master/Slave selection DIP switch
S2. Ensure that the master LED
(green) is illuminated on the master
CDBR unit.
• Check brake activation level switch
S3 for proper setting.
• Observe the Master and Slave
LEDs when using slave units. The
LEDs should blink when the CDBR
is activating.
The braking unit is damaged.
Replace the CDBR braking unit.
Problems
Cause
Possible Solution