4.3 The Drive and Programming Modes
74
YASKAWA EUROPE SIEP
YASKAWA AC Drive L1000V Technical Manual
u
Simplified Setup Using the Setup Group
In the Setup Group, the drive lists the basic parameters needed to set up the drive for an elevator application. This group
expedites the startup process by showing only the most commonly used parameters in lift commissioning.
n
Using the Setup Group
illustrates how to enter and how to change parameters in the Setup Group.
In this example, the Setup Group is accessed to change D1-02 from 0.00 Hz to 20.00 Hz. This changes the multi-step
frequency 2 which can be selected using the drive’s digital inputs.
Figure 4.6
Figure 4.6 Setup Group Example
STOP
Select digit
to edit
Frequency reference
appears when powered up
Press until
appears
Press until
d1-02 appears
Displayed
shortly
Returns automatically
Change
value
Confirm
Change
accepted