5.6 F: Option Settings
5.6
F: Option Settings
♦ F1: Encoder/PG Feedback Settings
The F1 parameters are used to set the drive up for operation using a motor encoder option card. Note that all speed
feedback option cards must be connected to the CN5-C port.
■ F1-01: Encoder 1 Resolution
Sets the encoder resolution.
No.
Parameter Name
Setting Range
Default
F1-01
Encoder 1 Resolution
1 to 60000 ppr <1>
Determined by A 1-02
<1> In CLV/PM mode, the maxim um setting is 15000 ppr.
■ F1-02, F1-14: PG Open (PGo) Circuit Operation Selection, Detection Time
A PGo fault is triggered if the drive receives no pulse signal for longer than the time set in F1-14. Set the stopping
method for a PGo fault in parameter F1-02.
No.
Parameter Name
Setting Range
Default
F1-02
Operation Selection at PG Open Circuit (PGo)
0 to 3
1
F1-14
PG Open-Circuit Detection Time
0.0 to 10.0 s
2.0 s
Param eter F1-02 Settings:
Setting 0: Ramp to stop (uses the deceleration ramp set to C1-02)
Setting 1: Coast to stop
Setting 2: Fast Stop (uses the Fast Stop ramp set to C1-09)
Setting 3: Alarm only
N ote: Due to potential damage to m otor and machinery, the “A larm only” setting should be used only under special circumstances.
■ F1-03, F1-08, F1-09: Overspeed (oS) Operation Selection, Detection Level, Delay Time
An oS fault is triggered when the speed feedback exceeds the value set in F1-08 for longer than the time set in F1-09. Set
the stopping method for an oS fault in parameter F1-03.
No.
Parameter Name
Setting Range
Default
F1-03
Operation Selection at Overspeed (oS)
0 to 3
1
F1-08
Overspeed Detection Level
0 to 120%
115%
F1-09
Overspeed Detection D elay Time
0.0 to 2.0 s
0.0 s
Param eter F1-03 Settings:
Setting 0: Ramp to stop (uses the deceleration ramp set to C1-02)
Setting 1: Coast to stop
Setting 2: Fast Stop (uses the Fast Stop ramp set to C1-09)
Setting 3: Alarm only
Note: D ue to potential damage to m otor and machinery, refrain from using the “A larm only” setting except under special