32
YASKAWA
SIEP C730600 0MA BACnet/IP Technical Manual
Object ID
Object Name
(Network Display, if Different)
Modbus Register (Hex.)
Active Text
Inactive Text
PV Access
(BYP AUTO Mode Status)
BV83
Bypass DRIVE Mode Status
(BYP DRV Mode Status)
8784: Bit 3
ON
OFF
R
BV84
Bypass BYPASS Mode Status
(BYP BYPASS Mode Stat)
8784: Bit 4
ON
OFF
R
BV85
Bypass Emergency Run Bypass Status
(BYP Em-Over BYP Stat)
8784: Bit 5
ACTIVE
OFF
R
BV86
Bypass Emergency Run Drive Fwd
Status
(BYP Em-Over DRV Stat)
8784: Bit 6
ACTIVE
OFF
R
BV87
Bypass Safety Status
(BYP Safety Status)
8784: Bit 7
OPEN
CLOSED
R
BV88
Bypass BAS Interlock Status
(BYP BAS Interlk Stat)
8785: Bit 0
OPEN
CLOSED
R
BV89
Bypass Run Status
(BYP RUN Status)
8785: Bit 1
RUN
OFF
R
BV90
Bypass Fault Status
(BYP Fault Status)
8785: Bit 2
FAULT
OFF
R
BV91
Bypass Auto Transfer Status
(BYP Auto Xfer Status)
8785: Bit 3
ACTIVE
OFF
R
BV92
Bypass Remote Transfer Status
(BYP Remote Xfer Stat)
8785: Bit 4
ACTIVE
OFF
R
BV93
Bypass Energy Savings Status
(BYP Energy Save Stat)
8785: Bit 5
ACTIVE
OFF
R
BV94
Bypass Motor 1 Select Status
(BYP Motor 1 Sel Stat)
8785: Bit 6
SELECT
OFF
R
BV95
Bypass Motor 2 Select Status
(BYP Motor 2 Sel Stat)
8785: Bit 7
SELECT
OFF
R
BV96
Bypass Drive Fault Status
(BYP Drive Flt Status)
8786: Bit 0
FAULT
OFF
R
BV97
BYP Safety Status 2
(BYP Safety Status 2)
8786: Bit 1
OPEN
CLOSED
R
BV98
Bypass BAS Interlock Fault Status
(BYP BAS ILock Status)
8786: Bit 2
FAULT
OFF
R
BV99
Bypass External Fault Status
(BYP Ext Fault Stat)
8786: Bit 3
FAULT
OFF
R
Bypass Motor OL Status
(BYP Motor OL Stat)
8786: Bit 5
FAULT
OFF
R
Bypass Motor 1 External OL Status
(BYP Motor 1 OL Stat)
8786: Bit 6
FAULT
OFF
R
Bypass Motor 2 External OL Status
(BYP Mtr 2 OL Stat)
8786: Bit 7
FAULT
OFF
R
Bypass Brownout Detect Status
(BYP Brownout Detect)
8787: Bit 0
FAULT
OFF
R
Bypass Drive Comms Status
(BYP Drive Comms)
8787: Bit 2
FAULT
OFF
R
Bypass Loss of Load Status
(BYP Loss Of Load)
8787: Bit 5
FAULT
OFF
R
Option Board on Drive Status
(BYP Option Brd Comms)
8787: Bit 4
FAULT
OFF
R
*1
Drive only. For bypass, use BV58.
*2
Drive only. For bypass, use BV59.
*3
Use with caution because objects BV7 to BV11 will be logically ORed with the physical digital inputs. This can cause hard-wired
Normally Closed inputs to operate incorrectly.
*4
Bypass only. Command a drive forward run or a bypass run.
*5
Bypass only. Command a drive reverse run.
*6
Not available on Z1000U. Available on HV600 and HV600 Bypass drives.
*7
Set
b1-04 = 0
to use.
*8
Available on bypass only.