Technical Tip: 

iQPump1000 Setup Procedure for Use with Seametrics AG2000 Flow Meter 

Product(s):

 iQpump1000 

Doc. No. 

TN.iQp.04 

 

TN.iQp.04 ©2016 - Yaskawa America, Inc.  

Revision 1 -  2016-04 

 

Page 1 of 10 

 

 

SUMMARY 

This Technical Tip provides an example set-up for a Yaskawa iQpump1000 drive and a 
Seametrics AG2000 Flow Meter. 

Features of this system example: 

  Display flow rate 

  Check for high or low flow rates and provide a digital output/alarm/fault 

  Display accumulation of flow over time (volume) 

  Provide a digital output/alarm/fault for high accumulation totals 

  Provide constant pressure system 

  Limit flow rate to 500 gallons per minute (GPM) to avoid pumping off the well 

  Limit accumulation to 100,000 gallons per day (GPD) 

 

Figure 1: Example System Overview 

 
 

 

Summary of Contents for iQpump1000

Page 1: ...rive and a Seametrics AG2000 Flow Meter Features of this system example Display flow rate Check for high or low flow rates and provide a digital output alarm fault Display accumulation of flow over ti...

Page 2: ...pressure system Pull up Resistor 10 k Ohm 1 4 Watt 5 tolerance resistor PROCEDURE Warning Electrical Shock Hazard Do not allow unqualified personnel to perform work on the drive Installation maintenan...

Page 3: ...ute shielded signal cable from the meter to the iQpump1000 I O terminals Install pressure transducer if used Configure pressure regulation function if used Refer to iQpump1000 User Manual TOEPYAIP1W01...

Page 4: ...trics AG2000 Flow Meter Product s iQpump1000 Doc No TN iQp 04 TN iQp 04 2016 Yaskawa America Inc Revision 1 2016 04 Page 4 of 10 STEP 1 MAKE ELECTRICAL CONNECTIONS 1 1 Refer to Figure 2 Make electrica...

Page 5: ...00 1 4 Re install the JVOP 183 digital operator on the iQpump1000 drive STEP 2 VERIFY SIGNAL FROM FLOW METER TO IQPUMP1000 WARNING Sudden Movement Hazard Clear all personnel from the drive motor and m...

Page 6: ...plying power to prevent injury from unexpected motor rotation 2 3 Start the iQpump1000 by pressing the HAND key on the JVOP 183 To set HAND SPEED press ENTER and adjust P5 02 to set the speed to a kno...

Page 7: ...play to GPM for comparison Because the U1 24 display reads in HZ and the analog gauge reads GPM we must convert the U1 24 display to GPM for comparison Multiply the U1 24 display value by 60 secs 60 H...

Page 8: ...flow meter function This will disable all other H6 parameters P6 01 Flow Meter Scale 700 Sets flow meter maximum gpm gallons per minute flow rate 700 GPM maximum scaling is according to AG2000 300 fl...

Page 9: ...uires user reset after fault Set parameter P6 19 2 to cause a fault if limit set in P6 17 is reached Monitor Parameters 3 3 View iQPump1000 monitor parameters U1 83 through U1 87 to find current syste...

Page 10: ...eshooting AG2000 Flow Meter from Seametrics LT 65200290 042115 Problem Probable Cause Corrective action Blank display Dead battery Replace battery pack Flow rate steadily reads zero when there is flow...