192
YASKAWA
TM.iQp.02 iQpump Drive Programming Manual
P1-11
<0032>
0106H
Maximum SetPoint
Difference
Max Setpoint Diff
When the Drive is running and the difference between the setpoint and
the feedback exceeds the level in P1-11 for the time specified in P1-12,
the Drive will trip on a “Not Maintaining Setpoint (NMS)”. The Drive
will coast to a stop when a fault occurs. A value of 0 disables this
function. This function is only active during running while operating in
auto mode.
0.0 to
6000.0
(system
units P1-
02)
0.0
(system
units P1-
02)
Pump Quick
Setup
P1-12
<0032>
0107H
Not Maintaining Setpoint
and Loss of Prime Time
Setpoint-LOP Tim
Delay time before a Not Maintaining Setpoint or Loss of Prime Time
fault occurs. Pump protection criteria specified in P1-11 or P1-14 must
be met for the Drive to fault. The Drive will coast to a stop when a fault
occurs. A value of 0 disables both Loss of Prime and Not Maintaining
Setpoint faults.
0 to 3600
60 sec
Pump Quick
Setup
P1-13
0108H
Hysteresis Level
Hysteresis Level
Hysteresis Level used for low and high feedback alarm detection. See
function P1-07 and P1-09.
0.0 to
100.0
(system
units P1-
02)
0.0
(system
units P1-
02)
Programming
P1-14
0109H
Prime Loss Level
Prime Loss Level
Used to detect loss of prime in the pump. If output current drops below
this level for the time specified in P1-12 and the output frequency is at
fmax, a “Loss Of Prime” fault occurs. The Drive will coast to a stop
when a fault occurs.
0.0 to
1000.0
0.0 A
Pump Quick
Setup
P1-15
010AH
Low Water Input
Low Water Input
Sets the type of control operation
0: Closed at Low Water, (Closed indicates low water condition)
1: Open at Low Water, (Open indicates low water condition)
To use the low water function one of the digital inputs (H1-XX=85)
needs to be programmed. The low water input can be used for a low
water condition or in combination with the pre-charge function to
indicate the reservoir is filled. The low water input fault is only active
during running while operating in auto mode.
0 or 1
0
Programming
Pump Protection
P2-01
060AH
Sleep Level Type
Sleep Lvl Type
Sets the sleep type.
0: Output Frequency
1: Output Current
2: Feedback
Note:
Feedback depends on PID direction operation.
Displays a “Sleep” Alarm when active.
0 to 2
0
Pump Quick
Setup
P2-02
060BH
Sleep Level
Sleep Level
Sleep activates when selected level (P2-01) reaches programmed sleep
level for time specified in P2-03. The level type is determined by P2-
01. A value of 0 disables this function. This function is only active
during running while operating in auto mode.
Display Units for Sleep Level P2-02 when P2-01 is programmed for
the following:
P2-01=0: >Display based on “Hz”
P2-01=1: >Display based on “A”
P2-01=2: >Display based on P1-02 Selection
Note:
When P2-01 is set for a value of 2, display units will be
dependent on P1-02 setting.
0.0 to
6000.0
0.0
Pump Quick
Setup
P2-03
060CH
Sleep Delay Time
Sleep Delay Time
Delay time before Drive enters sleep mode when criteria is met as
defined by parameter P2-02.
0 to 3600
10 sec
Pump Quick
Setup
P2-04
060DH
Delta Sleep Feedback
Drop Level
D Fb Drop Level
When the Drive enters sleep mode, the software monitors the feedback
to detect a flow-no flow condition. If the PID Error (setpoint minus
feedback) exceeds the programmed level P2-04 within the
programmed time (P2-05) and the output frequency is greater than the
minimum frequency (P1-06), the sleep operation deactivates and the
Drive returns to normal operation. A value of 0 disables this function.
0.0 to
6000.0
(system
units P1-
02)
0.0
(system
units P1-
02)
Programming
P2-05
060EH
Feedback detection drop
time.
FB Drop DetTime
Defines the time window in which the software monitors the feedback
to detect a flow-no flow condition. Works in conjunction with
parameter P2-04.
0 to 3600
10 sec
Programming
P2-06
060FH
Sleep Mode: Cycling
Protection
Cycle Protection
Maximum number of cycles allowed within the time specified in P2-07
before the Drive initiates a “Pump Cycle Fault (PCF)”. One Cycle is
defined when the Drive transfers from normal operation in auto mode
to sleep mode. A value of 0 disables this function.
0 to 10
0
Programming
P2-07
0610H
Sleep Mode: Maximum
Cycling Protection Time
Max. Cycle Time
Maximum time allowed between cycles. When no cycling occurs
within the programmed time, the Drive will reset the internal cycle
register. Works in conjunction with P2-06.
0 to 3600
300 sec Programming
Denotes that parameter can be changed when the Drive is running.
Parameter
No.
Modbus
Address
Parameter Name
Digital Operator
Display
Description
Setting
Range
Factory
Setting
Menu
Location
Page
No.
Summary of Contents for iQpump Series
Page 1: ...iQpump Drive Programming Manual Document Number TM iQp 02...
Page 204: ...204 YASKAWA TM iQp 02 iQpump Drive Programming Manual THIS PAGE INTENTIONALLY LEFT BLANK...
Page 208: ...208 YASKAWA TM iQp 02 iQpump Drive Programming Manual THIS PAGE INTENTIONALLY LEFT BLANK...
Page 209: ...YASKAWA TM iQp 02 iQpump Drive Programming Manual 209 THIS PAGE INTENTIONALLY LEFT BLANK...