B.11 o: Operator Related Parameters
o parameters set up the digital operator displays.
u
o1: HOA Keypad Display Selection
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
o1-01
(0500) Drive Mode Unit
Monitor Selection
User Monitor Sel
Selects the content of the last monitor that is shown when
scrolling through Drive Mode display. Enter the last three digits
of the monitor parameter number to be displayed: U
o
-
oo
.
Default: 106
(Monitor U1-06)
Range: 104 to
904
o1-02
(0501) User Monitor Selection
after Power Up
Power-On Monitor
1: Frequency Ref
2: FWD/REV
3: Output Freq
4: Output Current
5: User Monitor
1: Frequency reference (U1-01)
2: Direction
3: Output frequency (U1-02)
4: Output current (U1-03)
5: User-selected monitor (set by o1-01)
Default: 1
Range: 1 to 5
o1-03
(0502)
Digital Operator
Display Selection
Display Unit Sel
0: 0.01 Hz
1: 0.01%
2: r/min
3: User Units
Sets the units the drive should use to display the frequency
reference and motor speed monitors.
0: 0.01 Hz
1: 0.01% (100% = E1-04)
2: r/min (calculated using the number of motor poles setting in
E2-04)
3: User-selected units (set by o1-09, o1-10 and o1-11)
Default: 0
Range: 0 to 3
o1-05
(0504) LCD Contrast Control LCD Contrast
Sets the brightness of the optional LCD operator.
Default: 3
Range: 0 to 5
o1-06
(0517)
User Monitor Selection
Mode
Monitor Mode Sel
0: 3 Mon Sequential
1: 3 Mon Selectable
Selects the monitors displayed on the second and third lines of
the digital operator display.
0: 3 Monitor Sequential (displays the next two sequential
monitors)
1: 3 Monitor Selectable (set by o1-07 and o1-08)
Default: 1
Range: 0, 1
o1-07
(0518)
Second Line Monitor
Selection
2nd Monitor Sel
Selects the monitor that is shown in the second line.
Enter the last three digits of the monitor parameter number to
be displayed: U
o
-
oo
. For example, set "403" to display
monitor parameter U4-03.
Note:
Parameter is effective only
when o1-06 is set to 1.
Default: 102
Range: 101 to
904
o1-08
(0519)
Third Line Monitor
Selection
3rd Monitor Sel
Selects the monitor that is shown in the third line.
Enter the last three digits of the monitor parameter number to
be displayed: U
o
-
oo
. For example, set "403" to display
monitor parameter U4-03.
Note:
Parameter is effective only
when o1-06 is set to 1.
Default: 191
Range: 101 to
904
o1-09
(051C)
Frequency Reference
Display Units
Fref Disp Unit
0: "WC:InchOfWater
1: PSI :lb/SqrInch
2: GPM:Gallons/Min
3:
°
F:DegFarenheit
4: CFM:Cubic ft/Min
5: CMH:Cubic m/Hr
6: LPH:Litres/Hr
7: LPS:Litres/Sec
8: Bar:Bar
9: Pa:Pascals
10:
°
C:DegCelsius
11: m: meters
12: ft: feet
13: LPM:Litres/Min
14: CMM:Cubic M/
Min
15: "Hg:Inch Mercury
25: No Unit
Sets unit display for the frequency reference parameters and
frequency related monitors when o1-03 = 3.
0: WC (Inch of water)
1: PSI (Pounds per square inch)
2: GPM (Gallons per minute)
3: F (Degrees Fahrenheit)
4: CFM (Cubic feet per minute)
5: CMH (Cubic meters per hour)
6: LPH (Liters per hour)
7: LPS (Liters per second)
8: Bar (Bar)
9: Pa (Pascal)
10: C (Degrees Celsius)
11: Mtr (Meters)
12: Ft (Feet)
13: LPM (Liters per minute)
14: CMM (Cubic meters per minute)
15: “Hg (inches of mercury)
25: None
Default: 25
Range: 0 to 15;
25
B.11 o: Operator Related Parameters
YASKAWA
TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
353
B
Parameter List
Summary of Contents for iQpump Micro CIMR-PW Series
Page 443: ......