10.5 Metasys N2 Communications
736
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Object ID
Object Name
Default
OFF (0) State
ON (1) State
BI 4
Fault Monitor
0
Not Faulted
Faulted
BI 5
Zero Speed
0
Not Zero Speed
Zero Speed
BI 6
Speed Agree
0
Not Speed Agree
Speed Agree
BI 7
Minor Fault
0
No Minor Fault
Minor Fault
BI 8
Major Fault
0
No Major Fault
Major Fault
BI 9
Communication Error Monitor
0
No Error
Error
BI 10
Digital Output 7 (TB1 1~3) (Z2-23)
0
OFF
ON
BI 11
Digital Output 8 (TB1 4~6) (Z2-24)
0
OFF
ON
BI 12
Digital Output 9 (TB1 7~9) (Z2-25)
0
OFF
ON
BI 13
Safety Interlock Monitor
0
Safety Clear Terminal 3 Closed
Safety Set Terminal 3 Open
BI 14
HAND/AUTO Reference Monitor
0
AUTO or OFF
HAND
BI 15
Digital Input DI-3 Monitor
0
OFF
ON
BI 16
Digital Input DI-4 Monitor
0
OFF
ON
BI 17
Digital Input DI-5 Monitor
0
OFF
ON
BI 18
Digital Input DI-6 Monitor
0
OFF
ON
BI 19
Digital Input DI-7 Monitor
0
OFF
ON
■
Metasys N2 Binary Output (BO) Summary
Table 10.18 Metasys N2 Binary Output Summary (Drive to Metasys N2)
Object ID
Object Name
Default
OFF (0) State
ON (1) State
BO 1
Run Forward Command
0
Stop
Forward
BO 2
Run Reverse Command
0
Stop
Reverse
BO 3
Serial Fault (EFB) Command
0
No Fault
Fault
BO 4
Fault Reset Command
0
No Reset
Reset
BO 5
Digital Input 3 (TB2-3) (Z2-03)
0
OFF
ON
BO 6
Digital Input 4 (TB2-4) (Z2-04)
0
OFF
ON
BO 7
Digital Input 5 (TB2-5) (Z2-05)
0
OFF
ON
BO 8
Digital Input 6 (TB2-6) (Z2-06)
0
OFF
ON
BO 9
Digital Input 7 (TB2-7) (Z2-07)
0
OFF
ON
BO10
Panel Lock
0
HAND and OFF Keys Enabled
HAND and OFF Keys Disabled
BO 11
Communication Fault Enable
0
CE Not Activated if Cable Loss
Occurs
CE Activated if Cable Loss Occurs
*1
When
Z3-12 = 0
, this input is disabled.
◆
Mailbox Functions
This section defines the Metasys N2 points that read and write parameters.
■
Reading a Parameter
Two points are defined for reading parameters:
•
AO 30 - Specifies the parameter to be read
•
AI 38 - Reports the value of the parameter specified in AO 30.
When this point is read, it retrieves data from the parameter and sends it to the controller
Example: Writing a value of 387 (183 hex) to AO 30 specifies parameter
b1-04
. Reading AI 38 returns the current
setting of parameter
b1-04
to the controller.
Summary of Contents for HV600
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...