C1: AUTO Mode
Setting Value
Function
Description
C1
AUTO Mode
The terminal activates when the drive is in AUTO Mode operation.
■
C2: OFF Mode
Setting Value
Function
Description
C2
OFF Mode
The terminal activates when the drive is in OFF Mode operation.
■
C3: Main Feedback Lost
Setting Value
Function
Description
C3
Main Feedback Lost
The terminal activates when the drive loses the main PID feedback.
■
C4: Backup Feedback Lost
Setting Value
Function
Description
C4
Backup Feedback Lost
The terminal activates when the drive loses the backup PID feedback.
■
100 to 1C4: Inverse Outputs of 0 to C4
Setting Value
Function
Description
100 to 1C4
Inverse Outputs of 0 to C4
Causes inverse output of the function for the selected MFDO. Uses the last two digits of 1xx to select which function to inversely
output.
For example, set
H2-xx = 10E
for the inverse output of
E [Fault]
.
◆
H3: Analog Inputs
WARNING!
Sudden Movement Hazard. Do test runs and examine the drive to make sure that the command references are correct.
If you set the command reference incorrectly, it can cause damage to the drive or serious injury or death.
Drives have two analog input terminals, terminals A1 and A2.
H3 parameters
select the functions set to these analog
input terminals and adjust signal levels.
shows the functions that you can set to analog input terminals. Use
H3-02 and H3-10 [MFAI Function
Selection]
to set functions.
Table 5.43 MFAI Setting Values
Setting
Value
Function
Ref.
0
Frequency Reference
1
Frequency Gain
2
Auxiliary Frequency Reference 1
3
Auxiliary Frequency Reference 2
4
Output Voltage Bias
5
Accel/Decel Time Gain
6
DC Injection Braking Current
7
Torque Detection Level
8
Stall Prevent Level During Run
9
Output Frequency Lower Limit
B
PID Feedback
C
PID Setpoint
D
Frequency Bias
Setting
Value
Function
Ref.
E
Motor Temperature (PTC Input)
F
Not Used
16
Differential PID Feedback
1F
Not Used
24
PID Feedback Backup
25
PI2 Control Setpoint
26
PI2 Control Feedback
27
PI Auxiliary Control Feedback
2B
Emergency Override PID Feedback
2C
Emergency Override PID Setpoint
2D
Differential Level Source
2E
Hand Frequency Ref or Setpoint
Summary of Contents for HV600
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...