YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
189
The bypass uses a communications option card or input option card connected to the bypass control board to enter the
Run command.
Refer to the instruction manual included with the option card to install and set the option card.
Note:
If
b1-02 = 3
, but you did not connect an communications option card,
oPE05 [Run Cmd/Freq Ref Source Sel Err]
will flash on the keypad.
7 : AUTO C Term Run
The bypass uses the AUTO Command to put the bypass into AUTO Mode, and uses the terminal set for Run
[Z2-xx =
21, 37]
to enter the Run command.
8 : AUTO C Serial Run
The bypass uses the AUTO Command to put the bypass into AUTO Mode, and uses the Serial Run command
(register 0001) to enter the Run command.
9 : AUTO C Option Run
The bypass uses the AUTO Command to put the bypass into AUTO Mode, and uses a communications option card
connected to the bypass control board to enter the Run command.
■
b1-03: Stopping Method Selection
No.
(Hex.)
Name
Description
Default
(Range)
b1-03
(0182)
Stopping Method Selection
Sets the method to stop the motor after removing a Run command or entering a Stop command.
1
(0 - 3)
Select the applicable stopping method for the application from these four options:
0 : Ramp to Stop
When you enter the Stop command or turn OFF the Run command, the drive ramps the motor to stop.
The drive ramps the motor to stop as specified by the deceleration time. The default setting for the deceleration time
is
C1-02 [Deceleration Time 1]
. The actual deceleration time changes as the load conditions change (for example,
mechanical loss and inertia).
If the output frequency is less than or equal to the value set in
b2-01 [DC Injection/Zero SpeedThreshold]
during
deceleration, the drive will do DC Injection Braking.
•
Ramp to Stop
Parameter
b2-01
sets the frequency to start DC Injection Braking at stop. If the output frequency is less than or
equal to the value set in
b2-01
during deceleration, the drive will do DC Injection Braking for the time set in
b2-04
[DC Inject Braking Time at Stop]
.
b2-01: DC Injection/Zero SpeedThreshold
b2-04: DC Inject Braking Time at Stop
E1-09: Minimum Output Frequency
Figure 5.3 Ramp to Stop
Note:
When
b2-01 ≤ E1-09 [Minimum Output Frequency]
, the drive will start DC Injection Braking from the frequency set in
E1-09
.
1 : Coast to Stop
When you enter the Stop command or turn OFF the Run command, the drive turns OFF the output and coasts the
motor to stop.
Summary of Contents for HV600
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...