When NetRef or ComRef are the frequency reference source, the multi-step speed reference (2-step speed through 16-
step speed references) and the Jog Frequency Reference (JOG command) are enabled, and you can change the
frequency reference.
■
F6-08: Comm Parameter Reset @Initialize
No.
(Hex.)
Name
Description
Default
(Range)
F6-08
(036A)
Comm Parameter Reset
@Initialize
Sets the function to initialize
F6-xx and F7-xx parameters
when the drive is initialized with
A1-03
[Initialize Parameters]
.
0
(0, 1)
0 : No Reset - Parameters Retained
1 : Reset Back to Factory Default
Note:
When you use
A1-03
to initialize the drive, this setting will not change.
■
F6-14: BUS Error Auto Reset
No.
(Hex.)
Name
Description
Default
(Range)
F6-14
(03BB)
BUS Error Auto Reset
Sets the automatic reset function for
bUS [Option Communication Errors]
.
0
(0, 1)
0 : Disable
1 : Enabled
■
F6-15: Comm. Option Parameters Reload
No.
(Hex.)
Name
Description
Default
(Range)
F6-15
(0B5B)
Comm. Option Parameters
Reload
Sets the update method when you change
F6-xx, F7-xx [Communication Options]
.
0
(0 - 2)
Note:
•
Set
F6-15 = 0, 1
to reload
F6-xx
,
F7-xx
.
•
Set
F6-15 = 0, 1
to reset the display on the keypad to
0
.
0 : Reload at Next Power Cycle
Restart the drive to update parameters.
1 : Reload Now
The changed parameters are updated without restarting the drive.
2 : Cancel Reload Request
Cancels
CyPo [Cycle Power to Accept Changes]
.
■
F6-16: Gateway Mode
No.
(Hex.)
Name
Description
Default
(Range)
F6-16
(0B8A)
Gateway Mode
Sets the gateway mode operation and the number of connected slave drives.
0
(0 to 4)
0 : Disabled
1 : Enabled: 1 Slave Drives
2 : Enabled: 2 Slave Drives
3 : Enabled: 3 Slave Drives
4 : Enabled: 4 Slave Drives
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV