TOEPYAIHV6002A HV600 Drive Programming
253
Note:
•
After Auto-Tuning, the value of
E1-13
=
E1-05 [Maximum Output Voltage]
.
•
When
E1-13 = 0.0
, use the value of
E1-05
to control the voltage.
◆
E2: Motor Parameters
E2 parameters [Motor Parameters]
set induction motor data. To switch drive operation from one motor to another
motor, configure the first motor (motor 1).
Doing Auto-Tuning automatically sets the
E2 parameters
to the optimal values. If you cannot do Auto-Tuning, set the
E2 parameters
manually.
Note:
If you set
A1-02 [Control Method Selection]
to these control methods, the keypad will not show
E2-xx
:
•
5 [PM Open Loop Vector]
•
8 [EZ Vector Control]
■
E2-01: Motor Rated Current (FLA)
No.
(Hex.)
Name
Description
Default
(Range)
E2-01
(030E)
Motor Rated Current (FLA)
Sets the motor rated current in amps.
Determined by o2-04
(10% to 200% of the drive
rated current)
Note:
•
If
E2-01 < E2-03 [Motor No-Load Current]
the drive will detect
oPE02 [Parameter Range Setting Error]
.
•
The default settings and setting ranges are in these units:
–
0.01 A: 2011 to 2046, 4005 to 4014
–
0.1 A: 2059 to 2273, 4021 to 4302
The value set for
E2-01
becomes the reference value for motor protection and the torque limit. Enter the motor rated
current as written on the motor nameplate. The value of
E2-01
is automatically set to the value input for
“
Motor Rated
Current
”
by the Auto-Tuning process.
■
E2-02: Motor Rated Slip
No.
(Hex.)
Name
Description
Default
(Range)
E2-02
(030F)
Motor Rated Slip
Sets motor rated slip.
Determined by o2-04
(0.000 - 20.000 Hz)
This parameter value becomes the base slip compensation value. The drive automatically sets this parameter during
Auto-Tuning. When you cannot do Auto-Tuning, calculate the motor rated slip with the information on the motor
nameplate and this formula:
E2-02
= f - (n × p) / 120
•
f: Motor rated frequency (Hz)
•
n: Rated motor speed (min
-1
(r/min))
•
p: Number of motor poles
■
E2-03: Motor No-Load Current
No.
(Hex.)
Name
Description
Default
(Range)
E2-03
(0310)
Motor No-Load Current
Sets the no-load current for the motor in amps when operating at the rated frequency and the no-load
voltage.
Determined by o2-04
(0 to E2-01)
Note:
The default settings and setting ranges are in these units:
•
0.01 A: 2011 to 2046, 4005 to 4014
•
0.1 A: 2059 to 2273, 4021 to 4302
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV