YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
949
12.10 n: Special Adjustment
n parameters
set these functions:
•
Function to prevent hunting
•
High-slip braking
•
Motor line-to-line resistance online tuning
•
Fine-tune the parameters that adjust motor control
◆
n1: Hunting Prevention
The Hunting Prevention function will not let low inertia or operation with a light load cause hunting. Hunting
frequently occurs when you have a high carrier frequency and an output frequency less than 30 Hz.
■
n1-01: Hunting Prevention Selection
No.
(Hex.)
Name
Description
Default
(Range)
n1-01
(0580)
Hunting Prevention
Selection
Sets the function to prevent hunting.
Determined by o2-04
(0 to 2)
When drive response is more important than the decrease of motor vibration, disable this function.
If hunting occurs, or if you use a high carrier frequency or SwingPWM, set this parameter to 2 for better hunting
prevention.
0 : Disabled
1 : Enabled (Normal)
2 : Enabled (High Carrier Frequency)
■
n1-02: Hunting Prevention Gain Setting
No.
(Hex.)
Name
Description
Default
(Range)
n1-02
(0581)
Expert
Hunting Prevention Gain
Setting
Sets the performance of the hunting prevention function. Usually it is not necessary to change this
parameter.
1.00
(0.00 - 2.50)
Adjust this parameter in these conditions:
•
When
n1-01 = 1, 2 [Hunting Prevention Selection = Enabled (Normal), Enabled (High Carrier Frequency)]
: If
oscillation occurs when you operate a motor with a light load, increase the setting value in 0.1-unit increments.
•
When
n1-01 = 1, 2
, if the motor stalls: Decrease the setting value in 0.1-unit increments.
■
n1-03: Hunting Prevention Time Constant
No.
(Hex.)
Name
Description
Default
(Range)
n1-03
(0582)
Expert
Hunting Prevention Time
Constant
Sets the primary delay time constant of the hunting prevention function. Usually it is not necessary to
change this parameter.
Determined by o2-04
(0 - 500 ms)
Adjust this parameter in these conditions:
•
Load inertia is large: Increase the setting value. If the setting value is too high, response will be slower. Also, there
will be oscillation when the frequency is low.
•
Oscillation occurs at low frequencies: Decrease the setting value.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Summary of Contents for GA800 Series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...