11.19 Parameters that Change from the Default Settings with E3-01 [Motor 2 Control Mode Selection]
YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
595
11.19 Parameters that Change from the Default Settings with
E3-01 [Motor 2 Control Mode Selection]
The values for the parameters in these tables depend on the values for parameter
E3-01
. When you change the setting
for
E3-01
, the default settings will change.
No.
Name
Range
Unit
Motor 2 Control Method (setting value of E3-01)
V/f
(0)
CL-V/f
(1)
OLV
(2)
CLV
(3)
C3-21
Motor 2 Slip
Compensation Gain
0.0 - 2.50
0.1
0.0
-
1.0
1.0
C3-22
Motor 2 Slip Comp Delay
Time
0 - 10000
1 ms
2000
-
200
-
C5-21
Motor 2 ASR
Proportional Gain 1 (P)
0.00 - 300.00
0.01
-
0.20
-
20.00
C5-22
Motor 2 ASR Integral
Time 1 (I)
0.000 - 10.000
0.001 s
-
0.200
-
0.500
C5-23
Motor 2 ASR
Proportional Gain 2 (P)
0.00 - 300.00
0.01
-
0.02
-
20.00
C5-24
Motor 2 ASR Integral
Time 2 (I)
0.000 - 10.000
0.001 s
-
0.050
-
0.500
C5-26
Motor 2 ASR Delay Time 0.000 - 0.500
0.001 s
-
-
-
0.004
E3-04
Motor 2 Maximum
Output Frequency
40.0 - 590.0
0.1 Hz
60.0
60.0
60.0
60.0
E3-05
Motor 2 Maximum
Output Voltage
0.0 - 255.0
0.1 V
200.0
200.0
200.0
200.0
E3-06
Motor 2 Base Frequency
0.0 - 590.0
0.1 Hz
60.0
60.0
60.0
60.0
E3-07
Motor 2 Mid Point A
Frequency
0.0 - 590.0
0.1 Hz
3.0
3.0
3.0
-
E3-08
Motor 2 Mid Point A
Voltage
0.0 - 255.0
0.1 V
15.0
15.0
11.0
-
E3-09
Motor 2 Minimum Output
Frequency
0.0 - 590.0
0.1 Hz
1.5
1.5
0.5
0.0
E3-10
Motor 2 Minimum Output
Voltage
0.0 - 255.0
0.1 V
9.0
9.0
2.0
-
E3-11
Motor 2 Mid Point B
Frequency
0.0 - 590.0
Determined by
o1-04
0.0
0.0
0.0
0.0
E3-12
Motor 2 Mid Point B
Voltage
0.0 - 255.0
0.1 V
0.0
0.0
0.0
0.0
E3-13
Motor 2 Base Voltage
0.0 - 255.0
0.1 V
0.0
0.0
0.0
0.0
*1
This is the value for 200 V class drives. Double the value for 400 V class drives.
Summary of Contents for GA800 Series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...