6.3 MEMOBUS/Modbus Communications
278
YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
Figure 6.9 Message Example When Reading the Contents of Holding Register
■
Loopback Test
The loopback test uses function code 08 (Hex.) and returns the command message as a response message. This test
checks communication between the master and slave. The test code and data can use desired values.
shows examples of messages given out when the loopback test is done with the drive of slave 1.
Figure 6.10 Message Example When Doing the Loopback Test
■
Writing to Multiple Holding Registers
You can write the data that you set to the number of holding registers set in function code 10 (hex). You must
configure the number of the holding registers and each 8 higher bits and 8 lower bits in order in the command
message for the write data. You can write to a maximum of 16 holding registers.
shows example messages when you use the PLC to set Forward run in the drive of slave 1 with a 60.00
Hz frequency reference.
When you rewrite the parameter value with the write command through the
H5-11 [Comm ENTER Command Mode]
setting, you must use the Enter command to save and enable the contents of the changes. Refer to
ENTER Command Mode on page 889
and
for more information.
Summary of Contents for GA800 Series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...