4.10 Fine Tuning during Test Runs (Adjust the Control Function)
204
YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
Issue
Parameter Number
Possible Solutions
Default
Recommended Setting
•
Unsatisfactory motor torque
and speed response
•
Hunting or oscillation
C4-02 [Torque Compensation
Delay Time 1]
•
If torque or speed response are
slow, decrease the setting value
in increments of 2 ms.
•
If hunting or oscillation occur,
increase the setting value in
increments of 10 ms.
Note:
Make sure that this parameter
setting is:
C4-02 ≤ C4-06
[Motor 2 Torque Comp Delay
Time]
.
When you adjust
C4-02
, you
must also increase the
n2-02
[SpdFeedbackDetCtr (AFR)
TimeConst1]
value by the same
ratio.
20 ms
20 ms to 100 ms
•
Speed response is slow.
•
Speed is not stable.
C3-02 [Slip Compensation Delay
Time]
•
If speed response is slow,
decrease the setting value in
increments of 10 ms.
•
If speed is not stable, increase
the value in increments of 10
ms.
200 ms
100 ms to 500 ms
Speed precision is unsatisfactory.
C3-01 [Slip Compensation Gain]
•
If speed is too slow, increase the
setting value in increments of
0.1.
•
If speed is too fast, decrease the
setting value in increments of
0.1.
0.5 - 1.5
•
The volume of the motor
excitation sound is too high.
•
Hunting or oscillation at low
speeds (10 Hz or lower)
C6-02 [Carrier Frequency
Selection]
•
If the volume of the motor
excitation sound is too high,
increase the carrier frequency.
•
If hunting or oscillation occur at
low speeds, decrease the carrier
frequency.
1 (2 kHz)
0 to upper limit value
•
Torque at low speeds (10 Hz or
lower) is not sufficient. speed
response is slow.
•
Speed response is slow.
•
Large initial vibration at start
up.
•
E1-08 [Mid Point A Voltage]
•
E1-10 [Minimum Output
Voltage]
•
If torque or speed response are
slow, increase the setting value.
•
If there is large initial vibration
at start up, decrease the setting
value
Note:
If the setting value is set too
high, a large torque reference
may be output even with light
loads.
•
E1-08: 11.0 V
•
E1-10: 2.0 V
Default s/- 2 V
*1
The default setting changes when the settings for
A1-02 [Control Method Selection]
and
o2-04 [Drive Model (KVA) Selection]
change.
*2
The default setting changes when the settings for
A1-02 [Control Method Selection]
and
E1-03 [V/f Pattern Selection]
change.
*3
The default setting changes when the settings for
C6-01 [Normal / Heavy Duty Selection]
and
o2-04
change.
*4
Recommended settings are for 200 V class drives. Multiply the voltage by 2 for 400 V class drives.
◆
Closed Loop Vector Control Method
Table 4.19 Parameters for Fine Tuning the Drive (CLV)
Issue
Parameter Number
Possible Solutions
Default
Recommended Setting
•
Unsatisfactory motor torque
and speed response
•
Hunting or oscillation
•
High speed
C5-01 [ASR Proportional Gain
1]
•
Low speed
C5-03 [ASR Proportional Gain
2 (P)]
•
If torque or speed response are
slow, increase the setting value
in increments of 5.00.
•
If hunting or oscillation occur,
decrease the setting value.
20.00
10.00 - 50.00
•
High speed
C5-02 [ASR Integral Time 1]
•
Low speed
C5-04 [ASR Integral Time 2
(I)]
•
If torque or speed response are
slow, decrease the setting value.
•
If hunting or oscillation occur,
increase the setting value.
0.500 s
0.300 s to 1.000 s
The drive cannot find ASR
proportional gain or integral time
for low speed or high speed.
C5-07 [ASR Gain Switchover
Frequency]
Change the ASR proportional gain
and ASR integral time to conform
to the output frequency.
0.0 Hz
0.0 Hz to maximum output
frequency
Summary of Contents for GA800 Series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...