2.11 o: Keypad-Related Settings
520
YASKAWA
TOEPYAIGA8002B GA800 Drive Programming
■
o2-05: Home Mode Freq Ref Entry Mode
No.
(Hex.)
Name
Description
Default
(Range)
o2-05
(0509)
Home Mode Freq Ref Entry
Mode
Sets the function that makes it necessary to push the
to change the frequency reference value
with the keypad when in Drive Mode.
0
(0, 1)
0 : ENTER Key Required
You must push
to use the keypad to change the frequency reference value.
1 : Immediate / MOP-style
The frequency reference changes when you enter it with the keypad. This then changes the output frequency. It is not
necessary to push
. The drive keeps the frequency reference for 5 seconds after you use
and
on the
keypad to change the frequency reference value.
■
o2-06: Keypad Disconnect Detection
No.
(Hex.)
Name
Description
Default
(Range)
o2-06
(050A)
Keypad Disconnect
Detection
Sets the function that stops the drive if you disconnect the keypad connection cable from the drive or
if you damage the cable while the keypad is the Run command source.
1
(0, 1)
This parameter continues to operate if the keypad installed to the drive becomes disconnected.
This parameter is enabled in these conditions:
•
When
b1-02 = 0 [Run Command Selection 1 = Keypad]
or
b1-16 = 0 [Run Command Selection 2 = Keypad]
•
In LOCAL Mode
0 : Disabled
The drive continues operation when it detects a keypad disconnection.
1 : Enabled
The drive stops operation, detects
oPr [Keypad Connection Fault]
, and the motor coasts to stop when the drive
detects a keypad disconnection.
■
o2-07: Keypad RUN Direction @ Power-up
No.
(Hex.)
Name
Description
Default
(Range)
o2-07
(0527)
Keypad RUN Direction @
Power-up
Sets the direction of motor rotation when the drive is energized and the keypad is the Run command
source.
0
(0, 1)
This parameter is enabled in these conditions:
•
When
b1-02 = 0 [Run Command Selection 1 = Keypad]
or
b1-16 = 0 [Run Command Selection 2 = Keypad]
•
In LOCAL Mode
0 : Forward
1 : Reverse
■
o2-09: Region Code
No.
(Hex.)
Name
Description
Default
(Range)
o2-09
(050D)
Reserved
-
-
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV