2.2 A: Initialization Parameters
182
YASKAWA
TOEPYAIGA8002B GA800 Drive Programming
No.
Name
Optimal Value
C6-01
Normal / Heavy Duty Selection
0: Heavy Duty Rating
L3-04
Stall Prevention during Decel
1: Enabled
The drive saves the parameters in
as user parameters.
Table 2.7 Parameters Saved as User Parameters with the Conveyor Preset
User Parameter No.
Parameter No. Saved
Name
A2-01
A1-02
Control Method Selection
A2-02
b1-01
Frequency Reference Selection 1
A2-03
b1-02
Run Command Selection 1
A2-04
C1-01
Acceleration Time 1
A2-05
C1-02
Deceleration Time 1
A2-06
E2-01
Motor Rated Current (FLA)
A2-07
L3-04
Stall Prevention during Decel
3 : Exhaust Fan
The drive automatically sets the parameters in
for an exhaust fan application.
Table 2.8 Best Parameter Settings for Exhaust Fan Applications
No.
Name
Optimal Value
A1-02
Control Method Selection
0: V/f Control
b1-04
Reverse Operation Selection
1: Reverse Disabled
C6-01
Normal / Heavy Duty Selection
1: Normal Duty Rating
E1-03
V/f Pattern Selection
F: Custom
E1-07
Mid Point A Frequency
30.0 Hz
E1-08
Mid Point A Voltage
50.0 V
L2-01
Power Loss Ride Through Select
1: Enabled
L3-04
Stall Prevention during Decel
1: Enabled
The drive saves the parameters in
as user parameters.
Table 2.9 Parameters Saved as User Parameters with the Exhaust Fan Preset
User Parameter No.
Parameter No. Saved
Name
A2-01
b1-01
Frequency Reference Selection 1
A2-02
b1-02
Run Command Selection 1
A2-03
b1-04
Reverse Operation Selection
A2-04
b3-01
Speed Search at Start Selection
A2-05
C1-01
Acceleration Time 1
A2-06
C1-02
Deceleration Time 1
A2-07
E1-03
V/f Pattern Selection
A2-08
E1-07
Mid Point A Frequency
A2-09
E1-08
Mid Point A Voltage
A2-10
E2-01
Motor Rated Current (FLA)
A2-11
H1-05
Terminal S5 Function Selection
A2-12
H1-06
Terminal S6 Function Selection
A2-13
H1-07
Terminal S7 Function Selection
A2-14
L5-01
Number of Auto-Restart Attempts