1.21 Defaults by Drive Model and Duty Rating ND/HD
138
YASKAWA
TOEPYAIGA8002B GA800 Drive Programming
Name
Unit
Default
-
Drive Model
-
2110
2138
2169
2211
C6-01
Normal /
Heavy Duty
Selection
-
HD
ND
HD
ND
HD
ND
HD
ND
0
1
0
1
0
1
0
1
o2-04
Drive Model
(KVA)
Selection
Hex.
70
72
73
74
E2-11
(E4-11, E5-
02)
Motor Rated
Power
HP (kW)
30
(22)
40
(30)
40
(30)
50
(37)
50
(37)
60
(45)
60
(45)
75
(55)
E2-03
(E4-03)
Motor No-
Load Current
A
18.5
21.9
21.9
38.2
38.2
44
44
45.6
E2-05
(E4-05)
Motor Line-to-
Line
Resistance
Ω
0.079
0.064
0.064
0.039
0.039
0.03
0.03
0.022
E2-06
(E4-06)
Motor
Leakage
Inductance
%
19.5
20.8
20.8
18.8
18.8
20.2
20.2
20.5
E2-10
(E4-10)
Motor Iron
Loss
W
538
699
699
823
823
852
852
960
E5-01
PM Motor
Code Selection
-
FFFF
FFFF
FFFF
FFFF
FFFF
FFFF
FFFF
FFFF
L2-02
Power Loss
Ride Through
Time
s
2
2
2
2
2
2
2
2
L2-03
Minimum
Baseblock
Time
s
1
1.1
1.1
1.1
1.1
1.2
1.2
1.3
L2-04
Powerloss V/f
Recovery
Ramp Time
s
0.6
0.6
0.6
0.6
0.6
1
1
1
L2-05
Undervoltage
Detection Lvl
(Uv1)
-
190
190
190
190
190
190
190
190
L3-24
Motor Accel
Time for
Inertia Cal
s
0.355
0.323
0.323
0.32
0.32
0.387
0.387
0.317
L8-02
Overheat
Alarm Level
°C
105
105
115
115
105
105
105
105
L8-09
Output Ground
Fault
Detection
-
1
1
1
1
1
1
1
1
L8-38
Carrier
Frequency
Reduction
-
2
2
2
2
2
2
2
2
n1-01
Hunting
Prevention
Selection
-
2
2
2
2
2
2
2
2
n1-03
Hunting
Prevention
Time Constant
ms
10
10
10
10
10
10
10
10
n5-02
Motor Inertia
Acceleration
Time
s
0.355
0.323
0.323
0.32
0.32
0.387
0.387
0.317
*1