TOEPYAIGA8002B GA800 Drive Programming
117
No.
(Hex.)
Name
Description
MFAO Signal Level
U3-11 to U3-14
(0094 - 0097)
(080A - 080D)
ElapsedTime@1st to
4thFault
Shows the cumulative operation time when the first to fourth most recent faults occurred.
Unit: 1 h
Note:
The drive saves the
U3-11 to U3-14 [ElapsedTime@1st to 4thFault]
the cumulative operation
time to two types of registers at the same time for the MEMOBUS/Modbus communications.
No signal output available
U3-15 to U3-20
(080E - 0813)
ElapsedTime@5th to
10thFault
Shows the cumulative operation time when the fifth to tenth most recent faults occurred.
Unit: 1 h
No signal output available
◆
U4: Maintenance Monitors
No.
(Hex.)
Name
Description
MFAO Signal Level
U4-01
(004C)
Cumulative Ope Time
Shows the cumulative operation time of the drive.
Use parameter
o4-01 [Elapsed Operating Time Setting]
to reset this monitor. Use parameter
o4-02
[Elapsed Operating Time Selection]
to select the cumulative operation times from:
•
The time from when the drive is energized until it is de-energized.
•
The time at which the Run command is turned ON.
The maximum value that the monitor will show is
99999
. After this value is more than
99999
, the
drive automatically resets it and starts to count from
0
again.
Unit: 1 h
Note:
The MEMOBUS/Modbus communication data is shown in 10 h units. Use register 0099H for
data in 1 h units.
10 V: 99999 h
U4-02
(0075)
Num of Run Commands
Shows how many times that the drive has received a Run command.
Use parameter
o4-13 [RUN Command Counter @ Initialize]
to reset this monitor. The maximum
value that the monitor will show is
65535
. After this value is more than
65535
, the drive
automatically resets it and starts to count from
0
again.
Unit: 1
10 V: 65535 times
U4-03
(0067)
Cooling Fan Ope Time
Shows the cumulative operation time of the cooling fans.
Use parameter
o4-03 [Fan Operation Time Setting]
to reset this monitor. The maximum value that
the monitor will show is
99999
. After this value is more than
99999
, the drive automatically resets it
and starts to count from
0
again.
Unit: 1 h
Note:
The MEMOBUS/Modbus communication data is shown in 10 h units. Use register 009BH for
data in 1 h units.
10 V: 99999 h
U4-04
(007E)
Cool Fan Maintenance
Shows the cumulative operation time of the cooling fans as a percentage of the replacement life of
the cooling fans.
Use parameter
o4-03 [Fan Operation Time Setting]
to reset this monitor.
Unit: 1%
Note:
Replace the cooling fans when this monitor is 90%.
10 V: 100%
U4-05
(007C)
CapacitorMaintenance
Shows the operation time of the electrolytic capacitors for the main circuit and control circuit as a
percentage of the replacement life of the electrolytic capacitors.
Use parameter
o4-05 [Capacitor Maintenance Setting]
to reset this monitor.
Unit: 1%
Note:
Replace the electrolytic capacitor when this monitor is 90%.
10 V: 100%
U4-06
(07D6)
PreChargeRelayMainte
Shows the operation time of the soft charge bypass relay as a percentage of the replacement life of
the soft charge bypass relay.
Use parameter
o4-07 [Softcharge Relay Maintenance Set]
to reset this monitor.
Unit: 1%
Note:
Replace the drive when this monitor is 90%.
10 V: 100%
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV