H4: Analog Outputs
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
H4-01
(041D)
Terminal AM Analog
Output Select
Sets the monitoring number to be output from the MFAO terminal AM.
Set the
x-xx
part of the
Ux-xx [Monitor]
. For example, set
H4-01 = 102
to monitor
U1-02
[Output Frequency]
.
102
(000 - 999)
H4-02
(041E)
RUN
Terminal AM Analog
Output Gain
Sets the gain of the monitor signal that is sent from MFAO terminal AM.
Sets the analog signal output level from the terminal AM at 10 V or 20 mA as 100% when
an output for monitoring items is 100%.
100.0%
(-999.9 - +999.9%)
H4-03
(041F)
RUN
Terminal AM Analog
Output Bias
Sets the bias of the monitor signal that is sent from MFAO terminal AM.
When an output for monitoring items is 0%, this parameter sets the analog signal output
level from the AM terminal at 10 V or 20 mA as 0%.
0.0%
(-999.9 - +999.9%)
H4-07
(0423)
Terminal AM Signal
Level Select
Sets the MFAO terminal AM output signal level.
Note:
Make sure that you set jumper S5 on the control circuit terminal board when you
change these parameters.
0 : 0-10V
2 : 4 to 20 mA
0
(0, 2)
H4-20
(0B53)
Analog Power Monitor
100% Level
Sets the level at 10 V when
U1-08 [Output Power]
is set for analog output.
0.00 kW
(0.00 - 650.00 kW)
◆
H5: Modbus Communication
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
H5-01
(0425)
Drive Node Address
Sets the communication slave address for drives.
Note:
•
Re-energize the drive or set
H5-10 = 1 [Modbus Register 0025H Unit Sel= 1 V units]
after you change the parameter setting.
•
Setting 0 will not let the drive respond to MEMOBUS/Modbus communications.
1FH
(0 - FFH)
H5-02
(0426)
Communication Speed
Selection
Sets the communications speed for MEMOBUS/Modbus communications.
Note:
Re-energize the drive or set
H5-20 = 1 [Communication Parameters Reload = Reload
Now]
after you change the parameter setting.
0 : 1200 bps
1 : 2400 bps
2 : 4800 bps
3 : 9600 bps
4 : 19.2 kbps
5 : 38.4 kbps
6 : 57.6 kbps
7 : 76.8 kbps
8 : 115.2 kbps
3
(0 - 8)
H5-03
(0427)
Communication Parity
Selection
Sets the communications parity used for MEMOBUS/Modbus communications.
Note:
Re-energize the drive or set
H5-20 = 1 [Communication Parameters Reload = Reload
Now]
after you change the parameter setting.
0 : No parity
1 : Even parity
2 : Odd parity
0
(0 - 2)
H5-04
(0428)
Communication Error
Stop Method
Sets the motor Stopping Method when the drive detects
CE [MEMOBUS/Modbus
Communication Err]
issues.
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
3 : Alarm Only
3
(0 - 3)
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for GA500 series
Page 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...