2.8 H: Terminal Function Selection
YASKAWA
TOEPYAIGA5002A GA500 Programming
345
■
H4-07: Terminal AM Signal Level Select
No.
(Hex.)
Name
Description
Default
(Range)
H4-07
(0423)
Terminal AM Signal Level
Select
Sets the MFAO terminal AM output signal level.
0
(0, 2)
Note:
Set jumper S5 on the control circuit terminal block accordingly when changing these parameters.
0 : 0-10V
2 : 4 to 20 mA
■
H4-20: Analog Power Monitor 100% Level
No.
(Hex.)
Name
Description
Default
(Range)
H4-20
(0B53)
Analog Power Monitor
100% Level
Sets the level at 10 V when
U1-08 [Output Power]
is set for analog output.
0.00 kW
(0.00 - 650.00 kW)
Note:
•
When
H4-20 = 0.00 kW
, the output power monitor 10 V level = motor rated power (kW). The setting changes when the
A1-02 [Control
Method Selection]
value changes:
–
A1-02 = 0 [V/f]
:
E2-11 [Motor Rated Power]
–
A1-02 = 2 [OLV]
:
E2-11 [Motor Rated Power]
–
A1-02 = 5, 6 [OLV/PM, AOLV/PM]
:
E5-02 [PM Motor Rated Power]
–
A1-02 = 8 [EZOLV]
:
E9-07 [Motor Rated Power]
◆
H5: Memobus/Modbus Communication
H5 parameters
configure the drive to use MEMOBUS/Modbus communications.
You can use the MEMOBUS/Modbus protocol over the RS-485 port (terminals D+ and D-) in the drive to use serial
communication with programmable controllers (PLC).
■
H5-01: Drive Node Address
No.
(Hex.)
Name
Description
Default
(Range)
H5-01
(0425)
Drive Node Address
Sets the communication slave address for drives.
1FH
(0 - FFH)
Note:
•
Re-energize the drive or set
H5-10 = 1 [Modbus Register 0025H Unit Sel= 1 V units]
after you change the parameter setting.
•
Setting 0 will not let the drive respond to MEMOBUS/Modbus communications.
To enable the drive to communicate with the controller (master) over MEMOBUS/Modbus communications, you
must set the drive with a slave address. Set
H5-01 ≠ 0
.
Set a node address that is different from the master and other slave devices.
■
H5-02: Communication Speed Selection
No.
(Hex.)
Name
Description
Default
(Range)
H5-02
(0426)
Communication Speed
Selection
Sets the communications speed for MEMOBUS/Modbus communications.
3
(0 - 8)
Note:
Re-energize the drive or set
H5-20 = 1 [Communication Parameters Reload = Reload Now]
after you change the parameter setting.
0 : 1200 bps
1 : 2400 bps
2 : 4800 bps
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for GA500 series
Page 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...