YASKAWA
TOEPYAIGA5002A GA500 Programming
39
1.9
F: Options
◆
F1: Fault Detection in PG Speed Control
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
F1-02
(0381)
Encoder Signal Loss
Detect Sel
Sets the method to stop the motor or let the motor continue operating when the drive
detects
PGo [Encoder (PG) Feedback Loss]
.
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
3 : Alarm Only
4 : No Alarm Display
Note:
When
A1-02 = 0 [Control Method Selection = V/f]
, set
H6-01 = 3 [Terminal RP Pulse
Train Function = Speed Feedback (V/F Control)]
to enable this parameter.
1
(0 - 4)
F1-03
(0382)
Overspeed Detection
Selection
Sets the method to stop the motor or let the motor continue to operate when the drive
detects
oS [Overspeed]
.
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
3 : Alarm Only
Note:
When
A1-02 = 0 [Control Method Selection = V/f]
, set
H6-01 = 3 [Terminal RP Pulse
Train Function = Speed Feedback (V/F Control)]
to enable this parameter.
1
(0 - 3)
F1-04
(0383)
Speed Deviation
Detection Select
Sets the method to stop the motor or let the motor continue to operate when the drive
detects
dEv [Speed Deviation]
.
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
3 : Alarm Only
Note:
When
A1-02 = 0 [Control Method Selection = V/f]
, set
H6-01 = 3 [Terminal RP Pulse
Train Function = Speed Feedback (V/F Control)]
to enable this parameter.
3
(0 - 3)
F1-08
(0387)
Overspeed Detection
Level
Sets the detection level of
oS [Overspeed]
as a percentage when the maximum output
frequency is 100%.
Note:
•
Parameter
A1-02 [Control Method Selection]
selects which parameter is the
maximum output frequency.
–
A1-02 ≠ 8 [EZOLV]
:
E1-04 [Maximum Output Frequency]
–
A1-02 = 8
:
E9-02 [Motor Max Revolutions]
•
When
A1-02 = 0 [Control Method Selection = V/f]
, set
H6-01 = 3 [Terminal RP
Pulse Train Function = Speed Feedback (V/F Control)]
to enable this parameter.
115%
(0 - 120%)
F1-09
(0388)
Overspeed Detection
Delay Time
Sets the length of time that the speed feedback must be more than the
F1-08
level to cause
oS [Overspeed]
.
Note:
When
A1-02 = 0 [Control Method Selection = V/f]
, set
H6-01 = 3 [Terminal RP Pulse
Train Function = Speed Feedback (V/F Control)]
to enable this parameter.
Determined by A1-02
(0.0 - 2.0 s)
F1-10
(0389)
Speed Deviation
Detection Level
Sets the detection level of
dEv [Speed Deviation]
as a percentage when the maximum
output frequency is 100%.
Note:
•
Parameter
A1-02 [Control Method Selection]
selects which parameter is the
maximum output frequency.
–
A1-02 ≠ 8 [EZOLV]
:
E1-04 [Maximum Output Frequency]
–
A1-02 = 8
:
E9-02 [Maximum Speed]
•
When
A1-02 = 0 [Control Method Selection = V/f]
, set
H6-01 = 3 [Terminal RP
Pulse Train Function = Speed Feedback (V/F Control)]
to enable this parameter.
10%
(0 - 50%)
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for GA500 series
Page 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...