68
YASKAWA
TOEPC7106170YB YASKAWA AC Drive GA500 Installation & Primary Operation
Model
Terminal
Recomm.
Gauge
AWG, kcmil
Applicable
Gauge
AWG, kcmil
Wire
Stripping
Length
mm
Terminal
Screw
Size and
Shape
Tightening
Torque
N
∙
m (lbf
∙
in)
2056
R/L1, S/L2, T/L3
4
10 - 2
18
M5
4.1 - 4.5
(36 - 40)
U/T1, V/T2, W/T3
4
10 - 2
18
M5
•
≤ AWG 10
2.3 - 2.5
(19.8 - 22)
•
AWG 8 ≤
4.1 - 4.5
(36 - 40)
-, +1, +2
2
8 - 2
18
M5
4.1 - 4.5
(36 - 40)
B1, B2
8
12 - 6
10
M4
1.5 - 1.7
(13.5 - 15)
6
8 - 4
-
M6
5.4 - 6.0
(47.8 - 53.1)
2070
R/L1, S/L2, T/L3
2
6 - 1
20
M6
5 - 5.5
(
45 - 49)
U/T1, V/T2, W/T3
2
8 - 1
20
M6
5 - 5.5
(
45 - 49)
-, +1, +2
1
6 - 1/0
20
M6
5 - 5.5
(
45 - 49)
B1, B2
8
12 - 6
10
M4
1.5 - 1.7
(13.5 - 15)
4
6 - 4
-
M6
5.4 - 6.0
(47.8 - 53.1)
*1