1.3 Parameter Table
72
YASKAWA ELECTRIC
TOEP C710687 03B FSDrive-MV1000 Parameter Guide
u
o: Operator Related Settings
These parameters are for controlling the various functions, features, and display of the digital operator.
n7-62
(31EBH)
Phase Synchronous
Output Upper Limit
Sets the upper output limit used in the control to synchronize the phases of
the commercial power supply voltage and drive output voltage as a
percentage, taking the maximum frequency (E1- 04) as 100%.
Default: 5%
Min: 0%
Max: 20%
n7-63
(31ECH)
Phase Synchronous
Output Lower Limit
Sets the lower output limit used in the control to synchronize the phases of
the commercial power supply voltage and drive output voltage as a
percentage, taking the maximum frequency (E1-04) as 100%.
Default: 5%
Min: 0%
Max: 20%
n7-64
(31EDH)
Power Supply Phase
Detection Bias
Sets the bias for the commercial power supply voltage phase detection value
in units of degrees.
Default: 0.0 deg
Min: -180.0 deg
Max: 180.0 deg
n7-65
(31EEH)
Phase Synchronous
Level
Sets the judgment level of the phase synchronization of the commercial
power supply voltage and drive output voltage in units of degrees.
Default: 3.0 deg
Min: 0.0 deg
Max: 30.0 deg
n7-76
(31F9H)
Power Supply
Synchronous Time
Limit
Sets the time limit for the synchronous processing for the commercial power
supply in seconds. If the power supply is not synchronized within the set
time limit, a fault will be detected and the operation will be stopped.
Default: 15.0 s
Min: 10.0 s
Max: 6000.0 s
n9: I/O Voltage Detection
n9-02
(31C0H)
Output Current
Detection Gain
Sets the gain for adjusting the output current detection value in 0.0001 units.
Default:
Min: 0.0001
Max: 2.0000
n9-70
(657H)
Output Voltage
Detection Gain
Sets the gain for adjusting the output voltage detection value in 0.0001 units.
Default: 1.0000
Min: 0.0000
Max: 2.0000
n9-71
(31D1H)
Input Current
Conversion
Coefficient
Sets the input current conversion coefficient in 0.0001 units.
Default:
Min: 0.0000
Max: 6.5535
n9-72
(659H)
Input Voltage
Detection Gain
Sets the gain for adjusting the input voltage detection value in 0.0001 units.
Default: 1.0000
Min: 0.0000
Max: 2.0000
<6> Default setting is determined by o2-04, Drive Model Selection.
No.
(Addr.)
Name
Description
Setting
Page
o1: Digital Operator Display Selection
o1-01
(500H)
Drive Mode Unit
Monitor Selection
Selects the content of the last monitor that is shown when scrolling through
Drive Mode display. Enter the last three digits of the monitor parameter
number to be displayed: U
-
.
Default: 106
(Monitor U1-06)
Min: 104
Max: 699
o1-02
(501H)
User Monitor
Selection after
Power Up
1: Frequency reference (U1-01)
2: Direction
3: Output frequency (U1-02)
4: Output current (U1-03)
5: User-selected monitor (set by o1-01)
Default: 1
Min: 1
Max: 5
No.
(Addr.)
Name
Description
Setting
Page
All Modes
common
All Modes
common
All Modes
common
All Modes
common
All Modes
common
All Modes
common
All Modes
common
All Modes
common
All Modes
common
All Modes
common_
All Modes
common_
MV1000ParameterGuide_E_conditional.book 72 ページ 2013年10月11日 金曜日 午後8時18分