1.3 Parameter Table
70
YASKAWA ELECTRIC
TOEP C710687 03B FSDrive-MV1000 Parameter Guide
u
n: Special Adjustment
The n parameters adjust more advanced performance characteristics such as Hunting Prevention and Speed Feedback
Detection Control.
L8-66
(3115H)
Output Voltage
Unbalance
Detection Level
Sets the level at which unbalance of the output voltage is detected in 0.1%
units (100%: 2400 V for the 2.4 kV class and 4160 V for the 4.16 kV class).
Default: 10.0%
Min: 0.0%
Max: 100.0%
L8-67
(3116H)
Output Voltage
Unbalance
Detection Time
Sets the time before output voltage unbalance is detected in 0.001 s units. If
the state in which the zero-phase voltage detection value exceeds the level
set to L8-66 continues for the time set to L8-67 or longer, VUB (output
voltage unbalance) is detected.
Default: 0.200 s
Min: 0.001 s
Max: 2.000 s
L8-86
(3100H)
Transformer
Overheat Alarm
(TMA) Operation
Selection
Sets the operation when a TMA (Transformer Overheat Alarm) is detected.
0: Ramp to stop over the time set for C1-02 (Deceleration Time)
1: Coast to stop
2: Fast Stop over the time set for C1-09 (Fast Stop Time)
3: Continue operation. TMA alarm is triggered.
Default: 3
Min: 0
Max: 3
L8-87
(3101H)
Transformer
Overheat Alarm
(TMA) Level
Sets the detection temperature for TMA alarm function in
°
C units.
Note:
An alarm is detected when the detected transformer
temperature reaches the value set here.
Default:
Min: 50
°
C
Max: 160
°
C
L8-88
(3102H)
Transformer
Overheat Fault
(TME) Level
Sets the detection temperature for TME fault function in
°
C units.
Min: 50
°
C
Max: 160
°
C
<3> Parameter setting value is not reset to the default value when the drive is initialized (A1-03 = 1110/2220).
<6> Default setting is determined by o2-04, Drive Model Selection.
<8> The setting range changes if the value of the motor rated capacity (E2-11) is changed by Auto-Tuning or manual setting.
<10> Default setting is determined by A1-02, Control Method Selection.
<12> The setting range for the acceleration and deceleration times is determined by the accel/decel time setting units in C1-10. For example, if the
accel/decel time setting units are set to 0.01 s (C1-10 = 0), the setting range becomes 0.00 to 600.00 s.
<16> Default setting is determined by A1-02, Control Method Selection, and o2-04, Drive Model Selection.
<20> The range upper limit is determined by E1-04, Maximum Output Frequency, and E1-04, Frequency Reference Upper Limit.
No.
(Addr.)
Name
Description
Setting
Page
n1: Hunting Prevention
n1-01
(580H)
Hunting Prevention
Selection
0: Disabled
1: Enabled
Default: 1
Min: 0
Max: 1
n1-02
(581H)
Hunting Prevention
Gain Setting
If the motor vibrates while lightly loaded, increase the gain by 0.1 until
vibration ceases. If the motor stalls, decrease the gain by 0.1 until the stalling
ceases.
Default: 1.00
Min: 0.00
Max: 2.50
n1-03
(582H)
Hunting Prevention
Time Constant
Sets the time constant used for Hunting Prevention.
Default:
Min: 0 ms
Max: 500 ms
n1-05
(530H)
Hunting Prevention
Gain while in
Reverse
Sets the gain used for Hunting Prevention. If set to 0, the gain set to n1-02 is
used for operation in reverse.
Default: 0.00
Min: 0.00
Max: 2.50
No.
(Addr.)
Name
Description
Setting
Page
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
CLV
V/f
OLV
common
CLV
V/f
OLV
common
CLV
V/f
OLV
common
common
CLV
V/f
OLV
MV1000ParameterGuide_E_conditional.book 70 ページ 2013年10月11日 金曜日 午後8時18分