2.2 b: Application
YASKAWA ELECTRIC
TOEP C710687 03B FSDrive-MV1000 Parameter Guide
117
Differential Feedback
The second PID feedback signal for differential feedback can come from the sources listed in
. The differential
feedback function is automatically enabled when a differential feedback input is assigned.
Table 2.11 PID Differential Feedback Sources
Note:
A duplicate allocation of the PID differential feedback input will result in an oPE alarm.
PID Differential Feedback Source
Setting
Analog input 1
Set H3-02 = 16
Analog input 2
Set H3-10 = 16