2.2 Mechanical Installation
56
YASKAWA ELECTRIC
TOEP C710687 02B FSDrive-MV1000 Instructions
Table 2.15 Transportation Procedure 2 (Class: 11 kV)
DANGER!
Do not remove bolts from the top of the transformer panel and fit hoisting tackle to lift it. Failure to comply could result in
deformation or falling of the transformer panel.
DANGER!
When lifting the transformer panel, take care to ensure that the housing is not damaged by contact with the ceiling plate
or other parts. Failure to comply could result in deformation of the transformer panel or damage to the ceiling plate.
Transportation Procedure
1. Insert wire ropes for lifting through the support hook installation openings on the top of the drive.
Figure 2.19
Figure 2.19 Inserting Wire Ropes for Lifting
2. Attach the wire ropes for lifting to the support hooks on the transformer to lift the transformer panel.
Figure 2.20
Figure 2.20 Suspension of Transformer Panel
3. Ensure that the hanging angle is 45
°±
15
°
.
Wire ropes for lifting
Drive
Front view
Top view
Support hook
installation
opening
Support hook
installation
opening
Transformer
support hooks
Front view
Hanging angle
of 45
°
±15
°