B.3 Parameter Table
368
YASKAWA ELECTRIC
SIEP C710616 35D YASKAWA AC Drive E1000 Technical Manual
■
d3: Jump Frequency
■
d4: Frequency Reference Hold and Up/Down 2 Function
■
d6: Field Weakening and Field Forcing
■
d7: Offset Frequency
◆
E: Motor Parameters
■
E1: V/f Pattern
d2-03
(293H)
Master Speed Reference Lower
Limit
Sets the lower limit for frequency references from analog inputs as a percentage of the
maximum output frequency.
Default: 0.0%
Min: 0.0
Max: 110.0%
No.(Addr.)
Name
Description
Setting
Page
d3-01
(294H)
<10> Default setting is determined by the control mode (A1-02).
Jump Frequency 1
Eliminates problems with resonant vibration of the motor/machine by avoiding continuous
operation in predefined frequency ranges. The drive accelerates and decelerates the motor
through the prohibited frequency ranges.
Setting 0.0 disables this function.
Parameters must be set so that d3-01
≥
d3-02
≥
d3-03.
Default: 0.0 Hz
Min: 0.0 Hz
Max: 200.0 Hz
d3-02
(295H)
Jump Frequency 2
d3-03
(296H)
Jump Frequency 3
d3-04
(297H)
Jump Frequency Width
Sets the dead-band width around each selected prohibited frequency reference point.
Default: 1.0 Hz
Min: 0.0 Hz
Max: 20.0 Hz
No.(Addr.)
Name
Description
Setting
Page
d4-01
(298H)
Frequency Reference Hold
Function Selection
0: Disabled. Drive starts from zero when the power is switched on.
1: Enabled. At power up, the drive starts the motor at the Hold frequency that was saved.
Default: 0
Min: 0
Max: 1
d4-10
(2B6H)
Up/Down Frequency Reference
Limit Selection
0: Lower Limit is Determined by d2-02 or Analog Input
1: Lower Limit is Determined by d2-02
Default: 0
Min: 0
Max: 1
No.(Addr.)
Name
Description
Setting
Page
d6-01
(2A0H)
Field Weakening Level
Sets the drive output voltage for the Field Weakening function as a percentage of the maximum
output voltage.
Enabled when a multi-function input is set for Field Weakening (H1-
= 63).
Default: 80%
Min: 0%
Max: 100%
d6-02
(2A1H)
Field Weakening Frequency Limit
Sets the lower limit of the frequency range where Field Weakening control is valid.
The Field Weakening command is valid only at frequencies above this setting and only when
the output frequency matches the frequency reference (speed agree).
Default: 0.0 Hz
Min: 0.0 Hz
Max: 200.0 Hz
No.(Addr.)
Name
Description
Setting
Page
d7-01
(2B2H)
Offset Frequency 1
Added to the frequency reference when the digital input “Frequency offset 1” (H1-
= 44) is
switched on.
Default: 0.0%
Min: -100.0%
Max: 100.0%
d7-02
(2B3H)
Offset Frequency 2
Added to the frequency reference when the digital input “Frequency offset 2” (H1-
= 45) is
switched on.
Default: 0.0%
Min: -100.0%
Max: 100.0%
d7-03
(2B4H)
Offset Frequency 3
Added to the frequency reference when the digital input “Frequency offset 3” (H1-
= 46) is
switched on.
Default: 0.0%
Min: -100.0%
Max: 100%
No.(Addr.)
Name
Description
Setting
Page
E1-01
(300H)
Input Voltage Setting
This parameter must be set to the power supply voltage.
WARNING! Drive input voltage (not motor voltage) must be set in E1-01 for the protective
features of the drive to function properly. Failure to do so may result in equipment damage and/
or death or personal injury.
Default: 200 V
Min: 155 V
Max: 255 V
No.(Addr.)
Name
Description
Setting
Page
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
OLV/PM
V/f
common_
TMonly
OLV/PM
V/f
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly