TOEPC71061723A YASKAWA AC Drive CR700 Quick Start Guide
75
Code
Name
Causes
Possible Solutions
rdEr
Error Reading Data
You tried to back up the data when
o3-02 = 0 [Copy
Allowed Selection = Disabled]
.
Set
o3-02 = 1 [Enabled]
and back up again.
vAEr
Voltage Class, Capacity Mismatch
The power supply specifications or drive capacity
parameter settings are different between the keypad
and the drive.
1.
Make sure that drive model and the value set in
o2-04 [Drive
Model (KVA) Selection]
agree.
2.
Restore the parameters.
vFyE
Parameters do not Match
The parameters that are backed up in the keypad
and the parameters in the drive are not the same.
1.
Restore or backup the parameter again.
2.
Verify the parameters.
14
Drive Specifications
Note:
•
Perform Rotational Auto-Tuning to achieve the specifications listed for OLV, CLV, and AOLV.
•
Install the drive in an environment that meets the required specifications for optimum product life.
Table 14.1 Control Characteristics
Item
Specification
Control Method
•
V/f Control
•
V/f Control w/ PG
•
Open Loop Vector Control
•
Closed Loop Vector
•
Advanced Open Loop Vector
Frequency Control
Range
•
Advanced Open Loop Vector Control (AOLV): 0.01Hz - 120 Hz
•
Closed Loop V/f Control(CL-V/f), Closed Loop Vector Control (CLV): 0.01Hz - 400 Hz
•
V/f Control (V/f), Open Loop Vector Control (OLV): 0.01 Hz - 590 Hz
Frequency Accuracy
(Temperature
Fluctuation)
Digital inputs: Within ±0.01% of the maximum output frequency (-10 °C to +40 °C (14 °F to 104 °F))
Analog inputs: Within ±0.1% of the maximum output frequency (25 °C ±10 °C (77 °F ±18 °F))
Frequency Setting
Resolution
Digital inputs: 0.01 Hz
Analog inputs: 1/2048 of the maximum output frequency (11-bit signed)
Output Frequency
Resolution
0.001 Hz
Frequency Setting
Signal
Main speed frequency reference: -10 Vdc to +10 Vdc (20 kΩ), 0 Vdc to 10 Vdc (20 kΩ), 4 mA to 20 mA (250 Ω), 0 mA to 20 mA (250 Ω)
Starting Torque
•
V/f Control (V/f): 150%/3 Hz
•
Closed Loop V/f Control (CL-V/f): 150%/3 Hz
•
Open Loop Vector Control (OLV): 200%/0.3 Hz
•
Closed Loop Vector Control (CLV): 200%/0 min
-1
•
Advanced Open Loop Vector (AOLV): 200%/0.3 Hz
Note:
Drive capacity must selected appropriately to obtain this starting torque under Open Loop Vector Control (OLV), Closed Loop Vector Control (CLV),
and Advanced Open Loop Vector Control (AOLV).
Speed Control Range
•
V/f Control (V/f): 1:40
•
Closed V/f Control (CL-V/f): 1:40
•
Open Loop Vector Control (OLV): 1:200
•
Closed Loop Vector Control (CLV): 1:1500
•
Advanced Open Loop Vector Control (AOLV): 1:200
Zero Speed Control
Possible in Closed Loop Vector Control (CLV).
Torque Limits
Parameter settings allow separate limits in four quadrants in Open Loop Vector Control (OLV), Closed Loop Vector Control (CLV), and Advanced Open
Loop Vector Control (AOLV).
Accel & Decel Time
0.0 s to 6000.0 s
The drive allows four selectable combinations of independent acceleration and deceleration settings.
Braking Torque
Approx. 20%
Approx. 125% with a dynamic braking option
•
Short-time average deceleration torque
Motor output 0.4/0.75 kW: over 100%
Motor output 1.5 kW: over 50%
Motor output 2.2 kW and larger: over 20%, approximately 40% with overexcitation braking
•
Continuous regenerative torque: Approx. 20%. Dynamic braking option allows for approximately 125%, 10% ED, 10 s
Note:
•
Models 2003 to 2115 and 4002 to 4150 have a braking transistor.
•
Set
L3-04 = 0 [Stall Prevention during Decel = Disabled]
when using a regenerative converter, regenerative unit, braking unit, braking resistor, or
braking resistor unit. The drive may not stop within the designated deceleration time if
L3-04 = 0
.
•
Short-time average deceleration torque refers to the torque required to decelerate the motor (uncoupled from the load) from the rated speed to zero.
Actual specifications may vary depending on motor characteristics.
•
Continuous regenerative torque and short-time average deceleration torque for motors 2.2 kW and larger vary depending on motor characteristics.