94
YASKAWA
TOEPC7106170YB YASKAWA AC Drive GA500 Installation & Primary Operation
Table 11.4 Input Data for PM Motor Auto-Tuning
Input Data
Parameter
Unit
Auto-Tuning Mode
(T2-01 Setting)
PM Motor Parameter
Settings
(0)
PM
Stationary
Auto-
Tuning
(1)
PM Stationary
Auto-Tuning
for Stator
Resistance
(2)
Control Method
Selection
A1-02
-
5, 6
5
6
5
6
5, 6
PM Motor Code
Selection
T2-02
-
Motor code of
Yaskawa
motor
FFFF
FFFF
-
-
-
PM Motor Type
T2-03
-
-
-
-
x
x
-
PM Motor Rated
Power
T2-04
kW
-
x
x
x
x
-
PM Motor Rated
Voltage
T2-05
V
-
x
x
x
x
-
PM Motor Rated
Current
T2-06
A
-
x
x
x
x
x
PM Motor Base
Frequency
T2-07
Hz
-
x
-
x
-
-
Number of PM
Motor Poles
T2-08
-
-
x
x
x
x
-
PM Motor Base
Speed
T2-09
min
-1
-
-
x
-
x
-
PM Motor Stator
Resistance
T2-10
Ω
x
x
x
-
-
-
PM Motor d-Axis
Inductance
T2-11
mH
x
x
x
-
-
-
PM Motor q-Axis
Inductance
T2-12
mH
x
x
x
-
-
-
Back-EMF Units
Selection
T2-13
-
x
x
x
-
-
-
Back-EMF
Voltage Constant
(Ke)
T2-14
x
x
x
-
-
-
Pull-In Current
Level
T2-15
%
-
-
-
x
x
-
*1
Set the motor code for a Yaskawa PM motor.
*2