200
YASKAWA
TOEPC7106170YB YASKAWA AC Drive GA500 Installation & Primary Operation
Model
Terminal
Recomm.
Gauge
AWG, kcmil
Applicable
Gauge
AWG, kcmil
Wire
Stripping
Length
mm
Terminal
Screw
Size and
Shape
Tightening
Torque
N
∙
m (lbf
∙
in)
B006
L/L1, N/L2
12
14 - 10
8
M3
0.5 - 0.6
(4.4 - 5.3)
U/T1, V/T2, W/T3
14
14 - 12
8
M3
0.5 - 0.6
(4.4 - 5.3)
-, +1
12
14 - 10
8
M3
0.5 - 0.6
(4.4 - 5.3)
B1, B2
14
14 - 12
8
M3
0.5 - 0.6
(4.4 - 5.3)
10
14 - 10
-
M4
1.2 - 1.5
(10.6 - 13.3)
B010
L/L1, N/L2
10
12 - 10
8
M3
0.5 - 0.6
(4.4 - 5.3)
U/T1, V/T2, W/T3
14
14 - 12
8
M3
0.5 - 0.6
(4.4 - 5.3)
-, +1
10
12 - 10
8
M3
0.5 - 0.6
(4.4 - 5.3)
B1, B2
14
14 - 12
8
M3
0.5 - 0.6
(4.4 - 5.3)
10
14 - 10
-
M4
1.2 - 1.5
(10.6 - 13.3)
B012
L/L1, N/L2
8
14 - 8
10
M4
1.5 - 1.7
(13.5 - 15)
U/T1, V/T2, W/T3
12
14 - 10
10
M4
1.5 - 1.7
(13.5 - 15)
-, +1
8
14 - 8
10
M4
1.5 - 1.7
(13.5 - 15)
B1, B2
14
14 - 12
10
M4
1.5 - 1.7
(13.5 - 15)
10
14 - 10
-
M4
1.2 - 1.5
(10.6 - 13.3)
*1