60: DC Injection Braking Command
Setting Value
Function
Description
60
DC Injection Braking
Command
Sets the command to use DC Injection Braking to stop the motor.
If you input the Run command or JOG command, it will cancel DC Injection Braking.
shows the time chart of the DC Injection Braking function.
Figure 12.72 DC Injection Braking Time Chart
Note:
•
When
A1-02 = 8 [Control Method Selection = EZOLV]
, this function is available only when you use a PM motor.
•
Refer to "b2: DC Injection Braking and Short Circuit Braking" for more information.
■
61: Speed Search from Fmax
Setting Value
Function
Description
61
Speed Search from Fmax
Sets the function to start speed search using an external reference although
b3-01 = 0 [Speed Search Selection at Start =
Disabled]
.
When the terminal is turned ON for
b3-24 = 2 [Speed Search Method Selection = Current Detection 2]
, the drive
starts speed search from the maximum output frequency.
Note:
•
The drive will detect
oPE03 [Multi-Function Input Setting Err]
when
H1-xx = 61 and 62
are set at the same time.
•
Refer to
“
b3: Speed Search
”
for more information.
■
62: Speed Search from Fref
Setting Value
Function
Description
62
Speed Search from Fref
Sets the function to use an external reference to start speed search although
b3-01 = 0 [Speed Search Selection at Start =
Disabled]
.
When the terminal is turned ON for
b3-24 = 2 [Speed Search Method Selection = Current Detection 2]
, the drive
starts speed search from the frequency reference.
Note:
•
The drive will detect
oPE03 [Multi-Function Input Setting Err]
when
H1-xx = 61 and 62
are set at the same time.
•
Refer to
“
b3: Speed Search
”
for more information.
■
63: Field Weakening
Setting Value
Function
Description
63
Field Weakening
Sets the function to send the Field Weakening Level and Field Weakening Frequency Limit commands set in
d6-01[Field
Weakening Level] and d6-02 [Field Weakening Frequency Limit]
when the input terminal is activated.
Note:
Refer to
“
d6: Field Weak & Field Force
”
for more information.
■
65: KEB Ride-Thru 1 Activate (N.C.)
Setting Value
Function
Description
65
KEB Ride-Thru 1 Activate
(N.C.)
Sets operation of the KEB1 function through the KEB Ride-Thru 1 (N.C.).
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...