12.8 H: Terminal Function Selection
612
YASKAWA
SIEPC71061753A GA500 Technical Manual
Setting
Signal Input Method from
Peripheral Devices
External Fault Detection Method
Stopping Method
N.O.
N.C.
Always
Detected
Detected
during RUN
Only
Ramp to Stop
(Fault)
Coast to Stop
(Fault)
Fast Stop
(Fault)
Continuous
Operation
(Alarm Only)
25
-
x
x
-
-
x
-
-
26
x
-
-
x
-
x
-
-
27
-
x
-
x
-
x
-
-
28
x
-
x
-
-
-
x
-
29
-
x
x
-
-
-
x
-
2A
x
-
-
x
-
-
x
-
2B
-
x
-
x
-
-
x
-
2C
x
-
x
-
-
-
-
x
2D
-
x
x
-
-
-
-
x
2E
x
-
-
x
-
-
-
x
2F
-
x
-
x
-
-
-
x
*1
Set the terminal to N.O. (detects external fault when switched ON) or N.C. (detects external fault when switched OFF).
*2
Set the drive to always detect each fault or to detect only during run.
■
30: PID Integrator Reset
Setting Value
Function
Description
30
PID Integrator Reset
Sets the command to reset and hold the PID control integral to 0 when the terminal is ON.
Note:
Refer to
“
PID control block diagram
”
for more information.
■
31: PID Integrator Hold
Setting Value
Function
Description
31
PID Integrator Hold
Sets the command to hold the integral value of the PID control while the terminal is activated.
When you turn off the input terminal, PID control restarts the integral.
Note:
Refer to
“
PID control block diagram
”
for more information.
■
32: Multi-Step Speed Reference 4
Setting Value
Function
Description
32
Multi-Step Speed Reference
4
Uses speed references
d1-01 to d1-16
to set a multi-step speed reference.
Note:
Refer to "Setting Procedures for Multi-step Speed Operation
”
in
“
d: Reference Settings
”
for more information.
■
34: PID Soft Starter Disable
Setting Value
Function
Description
34
PID Soft Starter Disable
Sets the PID soft starter function.
ON : Disabled
Disables
b5-17 [PID Accel/Decel Time]
.
OFF : Enabled
Enables
b5-17 [PID Accel/Decel Time]
.
Note:
Refer to
“
PID control block diagram
”
for more information.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...