![YASKAWA CIPR-GA50C series Technical Manual Download Page 315](http://html2.mh-extra.com/html/yaskawa/cipr-ga50c-series/cipr-ga50c-series_technical-manual_3241765315.webp)
10.3 Model Specifications (Three-Phase 200 V Class)
YASKAWA
SIEPC71061753A GA500 Technical Manual
315
Model
2010
2012
2021
2030
2042
2056
2070
2082
Output
Rated Output
Capacity
(kVA)
HD
3
4.2
6.7
9.5
12.6
17.9
22.9
28.6
ND
3.7
4.6
8
11.4
16
21.3
26.7
31.2
Rated Output
Current (A)
HD
8.0
11.0
17.6
25.0
33.0
47.0
60.0
75.0
ND
9.6
12.2
21
30
42
56
70
82
Overload Tolerance
•
HD: 150% of the rated output current for 60 seconds. The permitted frequency of overload is once every 10 minutes.
•
ND: 110% of the rated output current for 60 seconds. The permitted frequency of overload is once every 10 minutes.
Note:
Derating may be necessary for applications that start and stop frequently.
Carrier Frequency
HD: 8 kHz without derating the drive capacity.
ND: 2 kHz without derating the drive capacity.
Derate the drive capacity to use values to 15 kHz maximum.
Maximum Output Voltage
Three-phase 200 V to 240 V
Note:
The maximum output voltage is proportional to the input voltage.
Maximum Output
Frequency
•
V/f, OLV, OLV/PM: 590 Hz
•
AOLV/PM: 270 Hz
•
EZOLV: 120 Hz
Measures for
Harmonics
DC reactor
External options
Braking
Device
Braking Transistor
Standard internal characteristics
EMC Filter
EMC Filter
IEC61800-3
Factory option
Models 2xxxE: Category C3 (Conducted emission)
Power
Supply
Rated Voltage/Rated
Frequency
•
Three-phase AC power supply 200 V to 240 V at 50/60 Hz
•
DC power supply 270 V to 340 V
Permitted Voltage
Fluctuation
-15% to +10%
Permitted Frequency
Fluctuation
±5%
Input Power
(kVA)
HD
3.4
5.0
8.7
11.0
17.0
24.0
31.0
44.0
ND
4.9
6.4
11
17.0
24.0
31.0
37.0
52.0
*1
The maximum applicable motor output complies with 208 V motor ratings as specified in NEC Table 430.250. The rated output
current of the drive output amps must be equal to or more than the motor rated current.
*2
The maximum applicable motor output is based on 4-pole, general-purpose 220 V motor ratings. The rated output current of the drive
output amps must be equal to or more than the motor rated current.
*3
The rated output capacity is calculated with a rated output voltage of 220 V.
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...