B.2 Parameter Tables
YASKAWA ELECTRIC
TOEP C710656 10B YASKAWA Power Regenerative Unit - R1000 Instruction Manual
147
Pa
ra
me
te
r L
is
t
B
◆
F: Options
F parameters program the regenerative unit for communication options and to function with option cards.
C7-15
(75AH)
Voltage Hysteresis
Width at Operation
Start/Stop
Vd Hysteresis
Normally, it is not necessary to change the setting of this
parameter. Adjusts the level to start regenerative operation
for automatic operation. Operation starts when the Voltage
Deviation (U1-73) exceeds the sum of C7-14 and C7-15.
Operation stops when Voltage Deviation goes below the
set value of C7-14.
200 V Class
Default: 3.0
Min.: 00.0
Max.: 50.0
400 V Class
Default: 6.0
Min.: 0.0
Max.: 100.0
C7-16
(75BH)
Minimum Operation
Time
Minimum On Time
Sets the minimum operation time from the start of
operation to when operation stops in automatic operation.
Default: 1.00 s
Min.: 0.00
Max.: 600.00
C7-43
(112AH)
Input Voltage Offset
Adjustment
Vac Bias Adj Sel
There is normally no need to change this parameter from
the default value. This parameter is for factory setting.
If the setting is not correct, the regenerative unit may be
damaged.
0: Standard
1: Start offset adjustment. (The parameter returns to 0 after
it is set.)
2: Offset adjustment not required. (The parameter returns
to 0 after it is set.)
Default: 0
Range: 0 to 2
C7-50
(113BH)
Operation Ready
ON Delay Time
Conv READY delay
Sets the delay time to turn on the Operation Ready signal
(H2-
=6).
Default: 0 ms
Min.: 0
Max.: 500
C7-53
(111FH)
Automatic
Operation Stop
Power
Autorun Power
Sets the power to stop the automatic operation. When in
automatic operation, Regenerative unit stops automatic
operation when the power becomes lower than
regenerative load.
Default: 50%
Min.: 0%
Max.: 100%
No.
(Address
Hex)
Name
LCD Display
Description
Values
F4: Analog Monitor Card (AO-A3)
F4-01
(391H)
Terminal V1
Monitor Selection
AO Ch1 Select
Sets the monitor signal for output from terminal V1. Set
this parameter to the last three digits of the desired
U
-
monitor. Some U parameters are available only
in certain control modes.
Default: 0
Min.: 000
Max.: 408
F4-02
(392H)
Terminal V1
Monitor Gain
AO Ch1 Gain
Sets the gain for voltage output via terminal V1.
Default: 100.0%
Min.: -999.9%
Max.: 999.9%
F4-03
(393H)
Terminal V2
Monitor Selection
AO Ch2 Select
Sets the monitor signal for output from terminal V2. Set
this parameter to the last three digits of the desired
U
-
monitor. Some U parameters are available only
in certain control modes.
Default: 0
Min.: 000
Max.: 408
F4-04
(394H)
Terminal V2
Monitor Gain
AO Ch2 Gain
Sets the gain for voltage output via terminal V2.
Default: 50.0%
Min.: -999.9%
Max.: 999.9%
F4-05
(395H)
Terminal V1
Monitor Bias
AO Ch1 Bias
Sets the amount of bias added to the voltage output via
terminal V1.
Default: 0.0%
Min.: -999.9%
Max.: 999.9%
F4-06
(396H)
Terminal V2
Monitor Bias
AO Ch2 Bias
Sets the amount of bias added to the voltage output via
terminal V2.
Default: 0.0%
Min.: -999.9%
Max.: 999.9%
No.
(Address
Hex)
Name
LCD Display
Description
Values
TOEP_C710656_10B_1_0.book 147 ページ 2015年1月8日 木曜日 午後8時55分